43
13 Servicing
13.7 Combustion Check
With the appliance operational c
onnect the CO
2
combustion
analyser to the test point, see diagram 13.9.
IMPORTANT:
Remember to replace the cap on
completion of the test.
Check the burner %CO
2
, at maximum rate(open a hot water
tap fully to generate a demand). The values are shown in the
“CHECK” column of the table and if the reading falls within
the range, disconnect the analyser, fit the test point cap and
return to functional checks - gas rate.
If adjustment is required remove the front and inner casing
panels, see diagram 13.1. Taking care not to touch any
internal components, then proceed as follows:
Press the “reset” button on the controls fascia, release
and immediately press and hold in the “+” button. After
approximately 5 seconds “Hi” will be displayed. Pressing
the mode button when “Hi” is selected will force the boiler
to maximum rate, the display will flash between “Hi” and the
“default display” this will indicate the boiler has been forced
to maximum.
Adjust the %CO
2
to the value shown in the “SETTING”
column of the table with the throttle, see diagram 12.5.
(Rotate anti-clockwise to increase).
To exit the check sequences press the “mode” and “+”
buttons simultaneously, this will reset the boiler to the default
display.
Check the burner % CO
2
at minimum rate is as shown in the
“CHECK” column of the table.
Press the “reset” button on the controls fascia, release
and immediately press and hold in the “+” button. After
approximately 5 seconds “Hi” will be displayed. Pressing the
“+” or “-” buttons will cycle between “Hi” and “Lo”. Pressing
the mode button when “Lo” is selected will force the boiler
to minimum rate, the display will flash between “Lo” and the
“default display” this will indicate the boiler has been forced
to minimum.
Adjustment of the %CO
2
at minimum rate is very coarse
so carefully adjust the %CO
2
to the value shown in the
“SETTING” column of the table with the offset adjustment,
see diagram 12.5 and %CO
2
Table (Rotate clockwise to
increase).
To exit the function press the “mode” and “+” buttons
simultaneously, this will reset the boiler to the default display.
13.8 Gas Rate Adjustment
This appliance incorporates a pre-mix burner and cannot be
adjusted, however, it is acceptible to set the combustion rate
with a gas analyser as described in section 13.7.
13.9 Inner Casing Panel Seal check
Check the condition of the seal, if worn or damaged remove
the seal and thoroughly clean the casing surface before fitting
the new seal, see diagram 13.10.
Refit the inner casing panel.
NOTE:
Ensure the seal is fitted correctly giving an airtight
joint.
13.10 Service Completion
On completion of the service the “Benchmark” Service Record
should be completed.
FLUE ELBOW
COMBUSTION
ANALYSER
SAMPLE POINT
VERTICAL FLUE
ADAPTOR
Diagram 13.9
13566
10063
INNER
CASING
PANEL
FRONT
CASING
PANEL
SEAL
Diagram 13.10
13872
MODEL
18sxi
30sxi
G31 BURNER % CO
2
CHECK
(case on)
SETTING
(case off)
9.2 to 10.2
10.0 to 11.0
10.1
10.5
+ 0.0
- 1.0
+ 0.3
- 0.8
MODEL
18sxi
30sxi
G20 BURNER % CO
2
CHECK
(case on)
SETTING
(case off)
8.5 to 9.6
8.5 to 9.6
9.1
9.1
+ 0.2
- 0.5
+ 0.2
- 0.5
Содержание 18sxi
Страница 30: ...30 10 Twin Flue Length Preparation and Installation Diagram 10 24 13226...
Страница 46: ...46 14 Fault Finding 13012 Diagram 14 5 CENTRAL HEATING...
Страница 48: ...48 14 Fault Finding 13447 Diagram 14 6 Fault Codes continued...
Страница 61: ...61 16 Spare Parts Diagram 15 21 13861 1 2 3 4 5 7 9 10 12 6 8 11 13...
Страница 63: ...63...