19
10.1 Flue Length
The maximum permissable horizontal flue length is 10 metres
plus the flue terminal assembly, this can be achieved by use
of the accessories, see diagram 10.3.
However should an additional 90o or 2 x 45o elbows be used
then the length MUST be reduced by 1metre.
The diagram 10.1 shows the length achievable by using the
kit A2043600.
10 Telescopic Flue - Length, Preparation and Installation
When extension pipes are used the flue system must be
designed to have a continuous fall to the boiler of at least
2.5o 44mm/metre to allow condensate to run back into the
boiler and out via the condensate drain.
The flue can be installed from inside the building, when
access to the outside wall face is not practicable.
Horizontal Telescopic Flue
Diagram 10.1
380 min. to 590 max.
WALL THICKNESS
BOILER
MOUNTING WALL
OUTSIDE
WALL FACE
203 min. to 413 max.
87min
65
112
176
NOTE. If necessary, it is permitted to increase
this dimension to 600mm max.
FLUE LENGTH
13558
L
FLUE
C
Min flue length 380mm
Max flue length 590mm
211
239
5mm
min.
clearance
A
A
Max.
distance from outside
wall face to min clearance.
LH - 346mm
RH - 374mm
Min.
distance from outside
wall face to min clearance.
LH - 136mm
RH - 164mm
OUTSIDE
WALL FACE
87min
NOTE. If necessary, it is permitted to
increase this dimension to 600mm max.
INTERNAL
SURFACE
13559
Содержание 18sxi
Страница 30: ...30 10 Twin Flue Length Preparation and Installation Diagram 10 24 13226...
Страница 46: ...46 14 Fault Finding 13012 Diagram 14 5 CENTRAL HEATING...
Страница 48: ...48 14 Fault Finding 13447 Diagram 14 6 Fault Codes continued...
Страница 61: ...61 16 Spare Parts Diagram 15 21 13861 1 2 3 4 5 7 9 10 12 6 8 11 13...
Страница 63: ...63...