Standard Horizontal Flue
10.6 Flue Length
The maximum permissable horizontal flue length is 10 metres
plus the flue terminal assembly, this can be achieved by use
of the accessories, see diagram 10.12.
However should additional 90o or 2 x 45o elbows be used
then the length MUST be reduced by 1metre.
The diagram 10.10 shows the length achievable by using the
kit A2043400.
When extension pipes are used the flue system must be
designed to have a continuous fall to the boiler of at least
2.5o 44mm/metre to allow condensate to run back into the
boiler and out via the condensate drain.
The flue can be installed from inside the building, when
access to the outside wall face is not practicable.
10 Standard Flue - Length, Preparation and Installation
Diagram 10.10
L
FLUE
C
Max flue length 730mm
211
239
5mm
min.
clearance
A
A
Max.
distance from outside
wall face to min clearance.
LH - 486mm
RH - 514mm
Min.
distance from outside
wall face to min clearance.
LH/RH - 75mm
OUTSIDE
WALL FACE
87min
NOTE. If necessary, it is permitted to
increase this dimension to 600mm max.
INTERNAL
SURFACE
WALL THICKNESS
BOILER
MOUNTING WALL
OUTSIDE
WALL FACE
75 min. to 554 max.
87min
112
176
NOTE. If necessary, it is permitted to increase
this dimension to 600mm max.
13560
Содержание 18sxi
Страница 30: ...30 10 Twin Flue Length Preparation and Installation Diagram 10 24 13226...
Страница 46: ...46 14 Fault Finding 13012 Diagram 14 5 CENTRAL HEATING...
Страница 48: ...48 14 Fault Finding 13447 Diagram 14 6 Fault Codes continued...
Страница 61: ...61 16 Spare Parts Diagram 15 21 13861 1 2 3 4 5 7 9 10 12 6 8 11 13...
Страница 63: ...63...