INSTALLATION

- 25 -

10.6 Range Rating - 38kW only

These boilers are fully modulating, therefore it is not 

necessary to range rate them, however, if desired, you can 

adjust the 38hxi boiler in 1kW increments between 10 and 

maximum output of your appliance, as described below.

Please refer to the table to check the gas  rates.

a) Press and hold the  ‘MODE’  button for 5 seconds.  The 

display will change to flashing  ‘0’.

b) Use the heating ‘+’  or  ‘-’  buttons to scroll to 96  (This is 

the installer level access password).

c) Press  ‘MODE’  to confirm, see diagnostic display 1.

d) Press  ‘MODE’  to change to the heating load value, see 

diagnostic display 2.

e) Use the  heating ‘+’  or  ‘-’  buttons to set the heating design 

value required.

f) Press the  ‘MODE’ button to confirm the diagnostic number 

flashes, see diagnostic display 1.

g) Hold ‘MODE’ for 5 seconds to save and exit.

10.7 Heating System

Check that all external controls are calling for heat.  The 

boiler will fire automatically. Fully open all radiator valves, flow 

control valve ‘A’ and bypass valve ‘B’, see diagram 5.3.

Balance the radiators as required and if fitted adjust valve ‘A’ 

to give the required system differential. Turn off all radiators 

that can be shut off by the user and check to see if less than 

the maximum differential allowed of 20

O

C can be achieved 

across flow and return.

Allow the system to reach maximum temperature then switch 

off the boiler by isolating from the electrical supply.

The pump overrun will continue for 5 mins.

Drain the entire system rapidly whilst hot, using the drain taps 

at all the low points of the system. Fill and vent the system as 

described previously.

Lock or remove the handle from control valve ‘A’ to prevent 

unauthorised adjustment.

10.8 Completion

Fit the base coverplate, see diagram 10.3.

Ensure that the magnetic lighting instruction label is placed on 

the surface of the boiler casing

Gb:

 It is a requirement that the “Benchmark” Installation, 

Commissioning and Service Record is completed and left with 

the user.

Ie:

 it is necessary to complete a “Declaration of Conformity” to 

indicate compliance to I.S.813. An example of this is given in 

the current edition of I.S.813.

10.9 Instruct the User

● Demonstrate, then instruct the User about the lighting 

procedure and heating system controls operation.

● Advise that to ensure the continued efficient and safe 

operation of the boiler it is recommended that it is checked 

and serviced at regular intervals. The frequency of servicing 

will depend upon the installation conditions and usage, but in 

general, once a year should be enough.

● Draw attention, if applicable, to the current issue of the Gas 

Safety (Installation and Use) Regulations, Section 35, which 

imposes a duty of care on all persons who let out any property 

containing a gas appliance in the UK.

● The user shall not interfere with or adjust sealed 

components.

● It is the Law that any servicing is carried out by a 

competent person

 approved at the time by the Health and 

Safety Executive.

COVER PLATE

Diagram 10.3

13540

● Advise the user that, like all condensing boilers this 

appliance will produce a plume of condensation from the flue 

terminal in cool weather. This is due to the high efficiency and 

hence low flue gas temperature of the boiler.

● Advise the user of the precautions necessary to prevent 

damage to the system, boiler and the building, in the event of 

the heating system being out of use during frost or freezing 

conditions.

● Advise the user that the permanent mains electrical supply 

SHOULD NOT be switched off, as the built in frost protection 

and pump saver program will not operate.

● Advise the User if the mains electricity and gas are to be 

turned off for any long periods during severe weather, it is 

recommended that the whole system, including the  boiler, 

should be drained to avoid the risk of freezing.

note: Sealed System

: Contact your installation/servicing 

company as draining, refilling and pressurising MUST be 

carried out by a 

competent person

 approved at the time by 

the Health and Safety Executive.

● Leave these instructions and the ‘Benchmark’ Installation, 

Commissioning and Service Record with the user.

13450

13451

kW

m3/hr

ft3/hr

kW

m3/hr

ft3/hr

24

2.5

88.3

38

4.06

143

23

2.4

84.8

37

3.9

138.5

22

2.3

81.2

36

3.8

135

21

2.2

77.7

35

3.7

131

20

2.1

74.2

34

3.6

127

19

2.0

70.6

33

3.5

124

18

1.9

67.1

32

3.4

120

17

1.8

63.6

31

3.3

117

16

1.7

60.0

30

3.2

113

15

1.6

56.5

29

3.1

109.5

14

1.5

53.0

28

3.0

106

13

1.4

49.5

27

2.9

102.4

12

1.3

45.9

26

2.8

98.9

11

1.2

42.4

25

2.6

91.8

10

1.12

38.9

Содержание 12 hxi G.C.No. 41-019-01

Страница 1: ...nstallation and Servicing Condensing Boilers Ultracom hxi 12 hxi G C No 41 019 01 15 hxi G C No 41 019 02 18 hxi G C No 41 019 03 24 hxi G C No 41 019 04 30 hxi G C No 41 019 05 38 hxi G C No 41 019 0...

Страница 2: ...guarantee registration card If your guarantee registration card is missing you can obtain a copy or record your registration by telephoning the Glow worm Customer Service number 01773 828100 Guarantee...

Страница 3: ...Water Condensate Connection 8 20 Electrical Connection 9 22 Commissioning 10 23 Servicing 11 27 Fault Finding 12 31 Replacement of Parts 13 38 Spare Parts 14 43 Manual Handling 15 44 Declaration of Co...

Страница 4: ...Keep load as close to body as possible Always use assistance if required Electrical Supply The boiler MUST be earthed All system components shall be of an approved type and all wiring to current I E E...

Страница 5: ...SHH The Current I E E Wiring Regulations Where no specific instructions are given reference should be made to the relevant British Standard Code of Practice In IE the installation must be carried out...

Страница 6: ...rnal to the house Release an ice blockage by the use of warm cloths on the pipe The boiler should then restart Condensate Drain A plastic drain pipe must be fitted to allow discharge of condensate to...

Страница 7: ...ta 7 13497 SEDBUK rating 2005 90 5 90 6 90 8 SEDBUK rating 2009 88 9 88 7 89 2 C13 C33 C43 C13 C33 C43 C13 C33 C43 C13 C33 C43 C13 C33 C43 C13 C33 C43 SEDBUK rating 2005 90 5 90 5 90 4 SEDBUK rating 2...

Страница 8: ...205 2 Boiler Dimensions Hydraulic Schematic All dimensions are given in millimetres except as noted The general arrangement of the boiler is shown in diagram 2 1 and the hydraulic and gas schematic di...

Страница 9: ...external access is not practicable consideration should be given for the space required to insert the flue internally which may necessitate clearance larger than those specified in diagram 3 1 3 3 Ti...

Страница 10: ...terminal must be exposed to the external air allowing free passage of air across it at all times Being a condensing boiler some pluming may occur from the flue outlet This should be taken into conside...

Страница 11: ...the terminal 300 I above adjacent ground or balcony level 300 J 2 from surface or a boundary facing the terminal 600 Position Position of the flue terminal mm L from opening door window in car port in...

Страница 12: ...t fitted 80 125 mm L 1 Key 1 Gasket fitted Type Max length 60 100 10 m 80 125 25 m Each time an additional 90 bend is necessary or 2 at 45 the length L must be reduced by 1 m 4 2 2 Vertical concentric...

Страница 13: ...e manufacturers instructions supplied The appliance maximum flue length must be included when calculating the overall design of the flue system NOTE The horizontal flue terminal must be removed MODEL...

Страница 14: ...0020107233_00 06 11 Glow worm INSTALLATION 14 12342 Diagram 5 1...

Страница 15: ...m should also be flushed Flushing should be carried out in accordance with BS7593 2006 using a cleanser such as Sentinel X300 or X400 Fernox Restorer or Salamander corrosion guard cleaner IMPORTANT En...

Страница 16: ...ing pump see the diagrammatic layout diagram 5 3 unless laid down differently by the manufacturer The expansion vessel volume depends on the total water system volume and the initial system design pre...

Страница 17: ...CONTROL VALVE TYPE CA BACKFLOW PREVENTION DEVICE BOILER RETURN FLOW BOILER RETURN FLOW Method 1 Diagram 5 4 11680 TEMPORARY CONNECTION HOSE UNION HOSE UNION SUPPLY PIPE CONTROL VALVE CONTROL VALVE DO...

Страница 18: ...tending the dashed inclined line on the template to the side wall This dashed line is drawn at 44mm metre 2 5 rise from the boiler Where this line reaches the side wall a horizontal line should be mar...

Страница 19: ...ue to the varied site conditions we do not supply fixings and advise that the installer should supply those which are suitable 7 2 Boiler Hanging IMPORTANT With regards to the Manual Handling Operatio...

Страница 20: ...ngs DO NOT use adhesive when connecting to the spigot The drain pipe should be non corrosive plastic IMPORTANT Please remove spigot bung before fitting condensate drain connection The condensate drain...

Страница 21: ...0020107233_00 06 11 Glow worm INSTALLATION 21 Diagram 8 3 13000...

Страница 22: ...spur box provided that it is not used in a room containing a fixed bath or shower The boiler is suitable for installation in bathroom zones 2 and 3 9 1 Electrical Wiring Remove the electrical cartrid...

Страница 23: ...e Health and Safety Executive and in accordance with the current issue of BS6798 DO NOT operate the boiler without water Make sure that the system has been thoroughly flushed out with cold water and t...

Страница 24: ...Central heating Boiler functions ALL switched off OFF 3 Turn ON your external controls and select the room temperature required The boiler will operate automatically NOTE The display will indicate th...

Страница 25: ...813 10 9 Instruct the User Demonstrate then instruct the User about the lighting procedure and heating system controls operation Advise that to ensure the continued efficient and safe operation of the...

Страница 26: ...nce does not light goes to lockout F1 turn the throttle anti clockwise a further turn and press the reset button The appliance will after a short delay again attempt to fire Repeat this procedure up t...

Страница 27: ...to touch any internal components proceed as follows Connect the CO2 combustion analyser to the relevant test point see diagram 11 1 Diagram 11 1 15442 G31 BURNER CO2 MODEL CHECK case on SETTING case...

Страница 28: ...ted this will force the boiler to minimum rate and the display will flash Lo indicating the boiler is operating at minimum Wait until the CO2 value is stable and check that the value is within the ran...

Страница 29: ...ctrode carefully from the combustion chamber see diagram 11 4 Inspect the tips for damage Clean away any debris and check the spark gap is 3 5 to 4 5 mm Check the electrode gasket for signs of damage...

Страница 30: ...the heat exchanger any remaining debris should pass through the condensate trap Ensure the water is kept away from electrical components 11 5 Inner Casing Panel Seal check Check the condition of the s...

Страница 31: ...10 5 Check that the heating system pressure indicates at least 1mb if not fill and vent the system as described in section 10 2 Check that all external controls are on Check the functional flow diagr...

Страница 32: ...0020107233_00 06 11 Glow worm MAINTENANCE 32 Diagram 12 4 13456...

Страница 33: ...0020107233_00 06 11 Glow worm MAINTENANCE 33 13012 Diagram 12 5 CENTRAL HEATING...

Страница 34: ...0020107233_00 06 11 Glow worm MAINTENANCE 34 13508 Diagram 12 6 Fault Codes...

Страница 35: ...ttons to scroll to 96 This is the installer level access password c Press MODE to confirm see diagnostic display 1 Use the or buttons to view the appropriate diagnostic number see diagram 12 7 If nece...

Страница 36: ...n Relay 1 Reserved for future use d 91 Internal Programmer type 0 24 hour default 1 7 day d 92 Enable Disable Internal Programmer 0 CH Off DHW Off default 1 CH Off DHW On 2 CH On DHW Off 3 CH On DHW O...

Страница 37: ...0020107233_00 06 11 Glow worm MAINTENANCE 37 Diagram 12 8 13568 STATE LISTS State list Accessed through Diagnostic Codes Level 1 Installer Access d 99...

Страница 38: ...the front of the inner front panel and lift off The side panels can be hinged sideways and removed to aid replacement of parts To hinge a side panel undo and remove the three screws securing each sid...

Страница 39: ...fan gas valve and burner assembly Remove the four screws that secure the burner see diagram 11 6 NOTE The burner will require a new gasket when refitted 13 8 Front Insulation For access refer to secti...

Страница 40: ...ve the float to clean it Remove any solids found Flush water through the trap to remove any remaining solids Check for any debris in the outlet hose of the condensate drain and clean as necessary 13 1...

Страница 41: ...Remove the electrical connections from the thermistor Remove the retaining clip from the flow pipe NOTE When reconnecting the polarity of the wiring to thermistors is not important 13 15 Heating Retur...

Страница 42: ...Remove electrical connection Gently ease back the retaining clips see diagram 13 13 Withdraw the board 13 19 Fuse Main PCB Control Box For access refer to section 13 16 The fuse is located at top lef...

Страница 43: ...ring from British Gas also quote the G C number of the part Key No Part No Description GC Part No 1 2000802463 Burner 12 15 18hxi E84021 1 2000802662 Burner 24 30 38hxi H36356 2 801655 Igniter E84015...

Страница 44: ...ton up and slide over polystyrene end packs Remove top polystyrene pack with fittings Positioning of Appliance for Final Installation no obstructions Recommend 2 persons lift appliance to position int...

Страница 45: ...0020107233_00 06 11 Glow worm MAINTENANCE 45...

Страница 46: ...a...

Страница 47: ...Number Comments Signature SERVICE 7 Date Energy Ef ciency Checklist completed Yes No Engineer Name Company Name Telephone Number Engineer ID Number Comments Signature SERVICE 9 Date Energy Ef ciency...

Страница 48: ...Belper Derbyshire DE56 1JT Because of our constant endeavour for improvement details may vary slightly from those shown in these instructions www glow worm co uk Subject to engineering changes 002010...

Отзывы: