Global Fires 70XT BF Скачать руководство пользователя страница 6

English

I N STA LLAT IO N M AN UAL

5.2 Connection

5.2.1 Gas connection

Place a gas tap in the gas pipe in accordance with the applicable regulations.
 

!Caution

Make sure there is no dirt in the gas pipes and connections.

No soldering may take place at the flexible gas hose(s), as this could cause leaks.

 
The following requirements apply to the gas connection:

use a gas pipe with the correct dimensions, so that no pressure loss can occur;

the gas tap must be approved (in the EU this will be the CE mark);

you should always be able to reach the gas tap.

5.2.2 Electric connection

In case of a 230 Volt electrical connection, provide proper grounding, if applicable.
Place this electrical connection away from the appliance, as low as possible in the chmney breast.
This has to do with the temperature development in the chimney breast.
If possible, place the receiver after any building work has been completed.
If this is not possible:

!Caution

Protect the receiver against dust and moisture created during the building process!

5.3 Placing the appliance

!Caution

Unless stated otherwise: always place the appliance with a minimum distance of 500 mm from combustible 
objects or materials;

Place the discharge pipes in such a way that situations with risk of fire can never occur;

Always place the appliance in front of a wall of non combustible and heat-resistant material;

Always maintain a minimum distance between appliance and back wall, if indicated in the dimensional 
drawing (Appendix 3, fig. 2);

Take sufficient measures to prevent high temperatures of a possible wall behind the chimney breast, 
including the materials and/or objects that are behind the wall;

Do not cover the appliance and/or do not wrap it in an insulation blanket or any other material;

Make sure that the appliance to be installed has a stable position. Attach the appliance, if applicable, to the 
wall using the wall brackets and/or fasten the extending legs with self-tapping screws.

!Caution

When installing an appliance that has to be built in, take the following into account:
The minimum construction dimensions according to Appendix 3, fig. 1 and 2.
 

Ø

Provide a gas connection at the location. For details (see section 5.2).

Ø

Make a passage for the flue gas discharge system or the concentric system with the following diameters; for 
details, see section 5.7 or 5.8:

the pipe di10 mm for a passage through non combustible material;

the pipe di100 mm for a passage through combustible material.

!Caution

Starting at section 5.9, you will find additional instructions that are specifically needed for the installation of your 
appliance.  

5.4 Placing a built in appliance

 (if applicable)

Not all DRU built in appliances are supplied with a control hatch. If not included in the delivery, this control hatch 
is available separately. In case of appliances with closed combustion (type C11/C31) we always recommend using 
the Dru control hatch. In case of appliances with open combustion (type B

11 AS/BS

), a control hatch is not required. 

In this section we assume an application with control hatch.

!Caution

If you do not use a recommended Dru control hatch, please strictly observe the safeguards and necessary 
instructions stated in chapters 5.4 to 5.6.
 
If you are not using the control hatch, please take the following into account as well:

the accessibility of components that are normally placed in the control hatch;

the maximum temperature of these components (maximum 55 °C).

 
The gas control is mounted under the appliance, at the burner mounting plate. It must be taken out and placed in 
the control hatch at a later time. For placing the gas control in the control hatch, see section 5.6.

6

Содержание 70XT BF

Страница 1: ...l i s h Store this document in a safe place Global 70XT BF 01 RCE Installation manual DRU 823266 EN US 0721 4 G20 G25 G25 3 Natural gas G31 Propane EN 959 118 01 EN Scan this QR Code for DRU Video As...

Страница 2: ...neral 5 8 2 Construction of the concentric system 5 8 3 Placing the concentric system 5 8 4 Connection existing chimney 5 9 Additional instructions 5 10 Glass pane 5 10 1 Removing the glass pane 5 10...

Страница 3: ...tely prior to installing this appliance If you use the DRU Powervent system or the DRU Smartvent system you must carefully and fully read and use the accompanying installation manual as well prior to...

Страница 4: ...re there is sufficient ventilation of the room where the appliance is installed according to legislation If you are installing an appliance with a closed combustion only use the concentric systems sup...

Страница 5: ...iance Check the appliance and accessories for damages during transport If necessary contact your supplier Never install an appliance that is damaged Remove any screws that are used to fix the applianc...

Страница 6: ...nket or any other material Make sure that the appliance to be installed has a stable position Attach the appliance if applicable to the wall using the wall brackets and or fasten the extending legs wi...

Страница 7: ...top of the chimney breast the material inside the chimney breast and the back wall of the chimney breast Make sure that the appliance is not carrying the weight of the chimney breast when using stone...

Страница 8: ...from dirt Reconnect the pipes to the gas control Caution Avoid kinks in the pipes Tighten the flexible gas pipe and the pilot burner pipe until they are gastight First tighten the thermocouple by hand...

Страница 9: ...wise Maintain a distance of at least 50 mm between the outside of the concentric system and the walls and or ceiling If the system is built in for instance a cove it should be made with non combustibl...

Страница 10: ...terminal the following applies The construction of the chosen system when using a roof terminal must be permissible according to Appendix 2 Table 5 See the method of working described below The worki...

Страница 11: ...the wall terminal from the outside by means of four screws Determine the remaining length for the wall or roof terminal and cut it to size make sure the correct insertion length is maintained Place th...

Страница 12: ...the 4 self tapping screws for the lower pane clamping strip C from the frame and remove the lower pane clamping strip Unscrew the middle 2 self tapping screws from the frame and remove the upper pane...

Страница 13: ...d point to the rear Adjust the position of the restrictor slide R using situations B to C in appendix 2 table 6 The letter of the position on the restrictor slide corresponds with the letter of the si...

Страница 14: ...g the vermiculite Caution The vermiculite should not get higher than the edge of the burner The burner deck has to remain covered with vermiculite in order to prevent reduction of the burner s life sp...

Страница 15: ...in order to avoid damaging the receiver Avoid formation of dust on or in the receiver cover it when performing work Place the receiver in its intended holder under the appliance or in the control hat...

Страница 16: ...ow position ignition and switching off Tip If the external control system has an intelligent clock function and or thermostat function the remote control supplied with the appliance should have the ma...

Страница 17: ...ches off after 22 seconds This happens because the appliance is equipped with a second thermocouple and the glass window has not been placed In this case you may presume that the main burner will cont...

Страница 18: ...he system as a result of pitting corrosion If required clean the following components the pilot burner malfunction search diagram Appendix 1 the space surrounding the pilot burner the glass pane s Cau...

Страница 19: ...door openers Instruct the user about the appliance and the remote control When the appliance is started for the first time point out that In order to avoid cracks in a chimney breast made of stone lik...

Страница 20: ...bend tip 1 mm higher Spark too weak thin and reddish Act as if no spark in box 2 05 and perform actions described for ignition cable and ignition electrode Pilot flame too weak dirty Remove injector r...

Страница 21: ...venly distributed across burner s chips on burner lack of combustion air See 2 15 cross lighting in low setting possible when thermostat function is used 2 15 Check Gas supply Supply pressure does not...

Страница 22: ...and brief noise of servomotor to confirm that communication code was set succesfully Remote control Battery 9V empty see indication on display Several After switching off going out the remote set is l...

Страница 23: ...ir inlet guide Key bolts M8x 140x50 Hexagonal nut M8 Washer M8 Spare self tapping screws for mounting the glass panes Socket spanner 8 mm Remote control with receiver 9V block battery Penlite battery...

Страница 24: ...0 65 2x 0 85 1 35 1 92 4 89 1 92 4 A Unit kW kW mg kWhinput GCV kW kW kW kW L h L h mbar mbar mm mm kW kW kW kW Type of heat output room temperature control Single stage heat output no room temperatu...

Страница 25: ...of meters vertical pipe length 0 8 4 0 51 0 8 Total number of meters horizontal pipe length excluding wall terminal 0 3 0 Table 4 Conditions for setting the appliance See Figure 4a 4b Air inlet guide...

Страница 26: ...l i s h INSTALLATION MANUAL 26 Table 5 Determining permissibility concentric system with roof terminal G20 G25 G25 3 Total number of meters horiz pipe length Total no of meters vertical and or sloping...

Страница 27: ...permissibility concentric system with roof terminal G31 Total number of meters horiz pipe length Total no of meters vertical and or sloping pipe length no bends 2 bends 3 bends 4 bends 5 bends Situat...

Страница 28: ...E n g l i s h INSTALLATION MANUAL Appendix 3 Figures 28 min 939 max 959 50 600 720 757 815 100 150 A A min 179 max 199 621 18 340 130 38C 2575 0 1...

Страница 29: ...g l i s h INSTALLATION MANUAL 29 min 15 max 100 min 342 761 min 177 625 min 560 B A C 38c 2576 0 250 700 C 2 2 B 2 2 A max 690 max 690 815 min 230 min 93 min 230 VOUT Tot min 200cm 2 VIN Tot min 80cm...

Страница 30: ...E n g l i s h INSTALLATION MANUAL 30 A B D C E 2x 38C 2587 0 1 2 3 4 5 1 2 6 4 3 5 38c 1078 3 0 3m 0 8 4m 38C 744ZJ 1x90 0 5 0 8m 0 m 38C 744ZZ 1x90 5 3 4a 4b...

Страница 31: ...E n g l i s h INSTALLATION MANUAL 31 U T S 38c 2577 0 R L G H M 38c 2578 0 7 6...

Страница 32: ...E n g l i s h INSTALLATION MANUAL 32 38P 0804 0 38P 0805 0 38p 0022 38P 0608 38P 0028 1 12 8 9 10 11...

Страница 33: ...E n g l i s h INSTALLATION MANUAL 33 38P 0806 0 A B C D E F G H A B 38P 0807 0 C 14 13...

Страница 34: ...E n g l i s h INSTALLATION MANUAL 34 38P 0808 0 F D 38P 0809 0 E 16 15...

Страница 35: ...E n g l i s h INSTALLATION MANUAL 35 H 38P 0810 0 G B V A S N 38p 0180 38p 0179 38p 0181 38 36 39 40 41...

Страница 36: ...E n g l i s h INSTALLATION MANUAL 36 38C 1940 5mV 38p 0182 122 A A 18 16 SECTION A A SCALE 1 3 38c 2579 0 44 42 43...

Страница 37: ...E n g l i s h INSTALLATION MANUAL 37...

Страница 38: ...E n g l i s h INSTALLATION MANUAL 38...

Страница 39: ...E n g l i s h INSTALLATION MANUAL 39...

Страница 40: ...E n g l i s h DRU Verwarming B V The Netherlands Postbus 1021 NL 6920 BA Duiven Ratio 8 NL 6921 RW Duiven EN...

Отзывы: