Global Fires 70XT BF Скачать руководство пользователя страница 21

English

INS T ALLAT I ON   M A N U A L 

2.12 Does appliance switch off 
exactly 22 sec after 
servomotor starts running?

2.19 

Replace gas control

(thermo-electric valve does not 
shut down quick enough because 
of some permanent magnetism).

2.14 Does main burner go out 
after 'some time'?

2.18 Can fire be switched off?

2.20 Perfect!
You have a well functioning 
fire

2.16 Is flame picture OK?

2.13 

Check cross lighting main 

burner and 2nd thermocouple 
system.
 
Measure voltage of 2nd 
thermocouple

-  Check voltage in mV, 22 sec after 

servomotor starts to run, c.q.  just 
before fire goes out. Glass window 
to be mounted!

-  Measure between black wire + earth 

point on gas control.

-  

Requirement:

 voltage >5 mV after 

rectification actions.

Voltage 0 mV

-  2nd couple defective.
-  Cross ligting main burner very slow. 

Take actions "Cross lighting too 
slow" (see  below), before taking any 
further action!!

Voltage <1,8 mV

-  Cross ligting main burner too slow. 

Take actions "Cross lighting too 
slow" (see below), before taking any 
further action!

-  2nd couple barred. Check:

- 2nd couple free of vermiculite, 
chips or pebbles;
- position of logs or pebbles;
- burner holes under 2nd couple 
open.

-  2nd couple defective (cross lighting 

OK, but voltage creeps up too slow).

-  Flames instable, see 2.15. Rectify, 

before any other action is taken!!

-  Burner pressure (too high or too 

low).

-  2nd couple not positioned correctly 

in flame.
Bend into correct position (see fig. 
43).

-  2nd thermocouple positioned 

correctly (see manual). Bend into 
flame (only if cross lighting and 
flame picture are OK!! See 2.17).

Voltage > 1,8 mV

-  Receiver defective. Replace.

Cross lighting of main burner too 
slow

Measure the time in sec from start 
running of servomotor till the flame 
reaches the 2nd couple.

Requirement:

 the flame must be in 

position at the 2nd couple <10 sec.
If not, check:
-  2nd couple free from vermiculite, 

chips or pebbles;

-  position of logs or pebbles;
-  burner holes (locally) blocked. 

Remove vermiculite dust.

-  vermiculite missing or not evenly 

distributed across burner(s);

-  chips on burner;
-  lack of combustion air. See 2.15.
-  cross lighting in low setting 

(possible when thermostat function 
is used).

2.15 Check

Gas supply

-  Supply pressure does not drop 

away as main burner (or other 
appliance) lights, causing pilot 
flame to shorten.

-  Burner pressure (too high or too 

low).

 

Flames instable (suffocating, lack 
of air).

Dancing flames on burner.
Lack of combustion air. Check:
-  flue system permissible;
-  proper flue terminal used, make 

should be 'DRU';

-  terminal correctly sited on roof or 

wall relative to obstructions;

-  integrity of flueing system (no 

interruptions, not barred, 
cobwebs);

-  air inlet guides;
-  flue restrictor/damper;
-  throttle rings.

See manual for specific 
requirements.

 

PowerVent®

Possibly not enough draught. Check 
if pressure difference set too high. 
Consult PowerVent® installation 
manual.
 

Pilot burner

-  Pilot burner dirty. Weak pilot 

flame being drawn away by 
flames main burner.
Clean with compressed air.
See 2.04.

2.17 Check

Flames: too low

-  Supply pressure does not drop 

away as main burner or other 
appliances in the building light, 
causing flames to shorten.

-  Burner pressure (too low).
-  False air: Check soundness glass 

window gasket/ soundness of the 
connection of the glass panes of 
two/three sided appliances (no 
slots allowed).

 

Flames: too high

-  Line pressure.
-  Burner pressure.
 

Flames: no even distribution or 
out on part of the burner(s) 

-  Position of logs or pebbles.
-  Burner holes (locally) blocked.

Remove vermiculite dust.

-  Vermiculite not distributed evenly 

across burner(s).

-  Adjustment of throttle ring(s).
 

Flames: too blue/too yellow or 
sooting

-  Air inlet guides.
-  Flue restrictor/damper.
-  Adjustment of throttle ring(s).
 

Flames: suffocating: lack of air

You see dancing flames on burner, 
seeking for air. See 2.15.
 

Flame picture 'restless'

Indication of too much draught. 
Check:
-  adjustment of appliance damper 

and air inlet guides);

-  vertical flue length allowed (<12 

m);

-  window glass not mounted gas 

tight.

 

PowerVent®? Check:

Possibly too much draught. Check:
-  Pressure difference set too high.
-  Silicon pressure measurement 

hoses leaking.

Consult PowerVent® installation 
manual for more info. 

no

no

yes

yes

no

yes

yes

no

21

Содержание 70XT BF

Страница 1: ...l i s h Store this document in a safe place Global 70XT BF 01 RCE Installation manual DRU 823266 EN US 0721 4 G20 G25 G25 3 Natural gas G31 Propane EN 959 118 01 EN Scan this QR Code for DRU Video As...

Страница 2: ...neral 5 8 2 Construction of the concentric system 5 8 3 Placing the concentric system 5 8 4 Connection existing chimney 5 9 Additional instructions 5 10 Glass pane 5 10 1 Removing the glass pane 5 10...

Страница 3: ...tely prior to installing this appliance If you use the DRU Powervent system or the DRU Smartvent system you must carefully and fully read and use the accompanying installation manual as well prior to...

Страница 4: ...re there is sufficient ventilation of the room where the appliance is installed according to legislation If you are installing an appliance with a closed combustion only use the concentric systems sup...

Страница 5: ...iance Check the appliance and accessories for damages during transport If necessary contact your supplier Never install an appliance that is damaged Remove any screws that are used to fix the applianc...

Страница 6: ...nket or any other material Make sure that the appliance to be installed has a stable position Attach the appliance if applicable to the wall using the wall brackets and or fasten the extending legs wi...

Страница 7: ...top of the chimney breast the material inside the chimney breast and the back wall of the chimney breast Make sure that the appliance is not carrying the weight of the chimney breast when using stone...

Страница 8: ...from dirt Reconnect the pipes to the gas control Caution Avoid kinks in the pipes Tighten the flexible gas pipe and the pilot burner pipe until they are gastight First tighten the thermocouple by hand...

Страница 9: ...wise Maintain a distance of at least 50 mm between the outside of the concentric system and the walls and or ceiling If the system is built in for instance a cove it should be made with non combustibl...

Страница 10: ...terminal the following applies The construction of the chosen system when using a roof terminal must be permissible according to Appendix 2 Table 5 See the method of working described below The worki...

Страница 11: ...the wall terminal from the outside by means of four screws Determine the remaining length for the wall or roof terminal and cut it to size make sure the correct insertion length is maintained Place th...

Страница 12: ...the 4 self tapping screws for the lower pane clamping strip C from the frame and remove the lower pane clamping strip Unscrew the middle 2 self tapping screws from the frame and remove the upper pane...

Страница 13: ...d point to the rear Adjust the position of the restrictor slide R using situations B to C in appendix 2 table 6 The letter of the position on the restrictor slide corresponds with the letter of the si...

Страница 14: ...g the vermiculite Caution The vermiculite should not get higher than the edge of the burner The burner deck has to remain covered with vermiculite in order to prevent reduction of the burner s life sp...

Страница 15: ...in order to avoid damaging the receiver Avoid formation of dust on or in the receiver cover it when performing work Place the receiver in its intended holder under the appliance or in the control hat...

Страница 16: ...ow position ignition and switching off Tip If the external control system has an intelligent clock function and or thermostat function the remote control supplied with the appliance should have the ma...

Страница 17: ...ches off after 22 seconds This happens because the appliance is equipped with a second thermocouple and the glass window has not been placed In this case you may presume that the main burner will cont...

Страница 18: ...he system as a result of pitting corrosion If required clean the following components the pilot burner malfunction search diagram Appendix 1 the space surrounding the pilot burner the glass pane s Cau...

Страница 19: ...door openers Instruct the user about the appliance and the remote control When the appliance is started for the first time point out that In order to avoid cracks in a chimney breast made of stone lik...

Страница 20: ...bend tip 1 mm higher Spark too weak thin and reddish Act as if no spark in box 2 05 and perform actions described for ignition cable and ignition electrode Pilot flame too weak dirty Remove injector r...

Страница 21: ...venly distributed across burner s chips on burner lack of combustion air See 2 15 cross lighting in low setting possible when thermostat function is used 2 15 Check Gas supply Supply pressure does not...

Страница 22: ...and brief noise of servomotor to confirm that communication code was set succesfully Remote control Battery 9V empty see indication on display Several After switching off going out the remote set is l...

Страница 23: ...ir inlet guide Key bolts M8x 140x50 Hexagonal nut M8 Washer M8 Spare self tapping screws for mounting the glass panes Socket spanner 8 mm Remote control with receiver 9V block battery Penlite battery...

Страница 24: ...0 65 2x 0 85 1 35 1 92 4 89 1 92 4 A Unit kW kW mg kWhinput GCV kW kW kW kW L h L h mbar mbar mm mm kW kW kW kW Type of heat output room temperature control Single stage heat output no room temperatu...

Страница 25: ...of meters vertical pipe length 0 8 4 0 51 0 8 Total number of meters horizontal pipe length excluding wall terminal 0 3 0 Table 4 Conditions for setting the appliance See Figure 4a 4b Air inlet guide...

Страница 26: ...l i s h INSTALLATION MANUAL 26 Table 5 Determining permissibility concentric system with roof terminal G20 G25 G25 3 Total number of meters horiz pipe length Total no of meters vertical and or sloping...

Страница 27: ...permissibility concentric system with roof terminal G31 Total number of meters horiz pipe length Total no of meters vertical and or sloping pipe length no bends 2 bends 3 bends 4 bends 5 bends Situat...

Страница 28: ...E n g l i s h INSTALLATION MANUAL Appendix 3 Figures 28 min 939 max 959 50 600 720 757 815 100 150 A A min 179 max 199 621 18 340 130 38C 2575 0 1...

Страница 29: ...g l i s h INSTALLATION MANUAL 29 min 15 max 100 min 342 761 min 177 625 min 560 B A C 38c 2576 0 250 700 C 2 2 B 2 2 A max 690 max 690 815 min 230 min 93 min 230 VOUT Tot min 200cm 2 VIN Tot min 80cm...

Страница 30: ...E n g l i s h INSTALLATION MANUAL 30 A B D C E 2x 38C 2587 0 1 2 3 4 5 1 2 6 4 3 5 38c 1078 3 0 3m 0 8 4m 38C 744ZJ 1x90 0 5 0 8m 0 m 38C 744ZZ 1x90 5 3 4a 4b...

Страница 31: ...E n g l i s h INSTALLATION MANUAL 31 U T S 38c 2577 0 R L G H M 38c 2578 0 7 6...

Страница 32: ...E n g l i s h INSTALLATION MANUAL 32 38P 0804 0 38P 0805 0 38p 0022 38P 0608 38P 0028 1 12 8 9 10 11...

Страница 33: ...E n g l i s h INSTALLATION MANUAL 33 38P 0806 0 A B C D E F G H A B 38P 0807 0 C 14 13...

Страница 34: ...E n g l i s h INSTALLATION MANUAL 34 38P 0808 0 F D 38P 0809 0 E 16 15...

Страница 35: ...E n g l i s h INSTALLATION MANUAL 35 H 38P 0810 0 G B V A S N 38p 0180 38p 0179 38p 0181 38 36 39 40 41...

Страница 36: ...E n g l i s h INSTALLATION MANUAL 36 38C 1940 5mV 38p 0182 122 A A 18 16 SECTION A A SCALE 1 3 38c 2579 0 44 42 43...

Страница 37: ...E n g l i s h INSTALLATION MANUAL 37...

Страница 38: ...E n g l i s h INSTALLATION MANUAL 38...

Страница 39: ...E n g l i s h INSTALLATION MANUAL 39...

Страница 40: ...E n g l i s h DRU Verwarming B V The Netherlands Postbus 1021 NL 6920 BA Duiven Ratio 8 NL 6921 RW Duiven EN...

Отзывы: