INS T ALLAT I ON M A N U A L
Place the concentric system as follows:
Ø
Build the system up from (the flue spigot of) the appliance.
Ø
Connect the concentric pipe pieces and, if necessary, the bend(s).
Ø
On each connection, apply a clip binding with silicon sealing ring.
Ø
Use a self-tapping screw to fix the clip binding to the pipe on locations that cannot be reached after installation.
Ø
Attach the concentric system with sufficient fastening brackets, so that the weight is not resting on the appliance.
Observe the following;
•
Place the first fastening bracket 0.5 metre from the appliance, at the most.
•
Place a fastening bracket maximum 0.1 metre from each bend, if the bends are more than 0.25 metre away
from each other. If two bends are closer to one another than 0.25 metre, 1 fastening bracket between these
bends will be sufficient.
•
At least every 1 metre, place a fastening bracket at slanted and horizontal sections.
•
At least every 2 metres, place a fastening bracket at vertical sections.
Ø
Fasten a roof terminal with anchor cables, if it protrudes more than 1,5 metres above the terminal.
Ø
Attach the wall terminal from the outside by means of four screws.
Ø
Determine the remaining length for the wall or roof terminal and cut it to size, make sure the correct insertion
length is maintained.
Ø
Place the wall terminal with the (groove/folded) seam at the top.
!Caution
When using the wall terminal, place the terminal with a downward slope of 1 cm / metre towards the outside, in
order to prevent rain water from raining in.
5.8.4 Connection to an existing chimney
It is possible to connect the appliance to an existing chimney.
A flexible SS pipe is placed in the chimney with a fitting diameter at the flue gas discharge pipe, for the discharge
of flue gas. The surrounding space is used to supply combustion air.
The following requirements apply when connecting to an existing chimney:
•
only allowed when used in combination with the special DRU chimney kit. The installation regulation is also
supplied;
•
the internal dimensions should be at least 150 x 150 mm;
•
the vertical length has a maximum of 12 metres;
•
the total horizontal pipe length may have a maximum length that you can find in Appendix 2, Table 4;
•
the existing chimney has to be clean;
•
the existing chimney has to be tight.
For adjusting the appliance, the same conditions/instructions apply as for the concentric system described above.
11
Содержание 70XT BF
Страница 31: ...E n g l i s h INSTALLATION MANUAL 31 U T S 38c 2577 0 R L G H M 38c 2578 0 7 6...
Страница 32: ...E n g l i s h INSTALLATION MANUAL 32 38P 0804 0 38P 0805 0 38p 0022 38P 0608 38P 0028 1 12 8 9 10 11...
Страница 33: ...E n g l i s h INSTALLATION MANUAL 33 38P 0806 0 A B C D E F G H A B 38P 0807 0 C 14 13...
Страница 34: ...E n g l i s h INSTALLATION MANUAL 34 38P 0808 0 F D 38P 0809 0 E 16 15...
Страница 35: ...E n g l i s h INSTALLATION MANUAL 35 H 38P 0810 0 G B V A S N 38p 0180 38p 0179 38p 0181 38 36 39 40 41...
Страница 37: ...E n g l i s h INSTALLATION MANUAL 37...
Страница 38: ...E n g l i s h INSTALLATION MANUAL 38...
Страница 39: ...E n g l i s h INSTALLATION MANUAL 39...
Страница 40: ...E n g l i s h DRU Verwarming B V The Netherlands Postbus 1021 NL 6920 BA Duiven Ratio 8 NL 6921 RW Duiven EN...