Page 9
INSTALLATION
Stainless Lite HP/Heat Pump Selection Guide
The table above can be used to match heat pumps to heat pump cylinders.
To use, first obtain the maximum flow rate from the heat pump manufacture’s
instructions, match this to the fl ow rates in section 1 and follow this fl ow rate’s column
down through the other sections.
Section 2 shows the velocity in the pipe work of different diameters at this fl ow rate. A
maximum fl ow velocity of 1m/s has been chosen to limit fl ow noise. Use this section to
choose the correct pipe diameter.
Stainless Lite HP/Heat Pump Selection Guide
1 - Flow rates in various units for comparison with heat pump manufacturers data
m
3
/h
0.50
0.75
1.00
1.25
1.50
1.75
2.00
2.25
2.50
2.75
3.00
3.25
3.50
3.75
4.00
4.25
l/min
8.33
12.50 16.67 20.83 25.00 29.17 33.33 37.50 41.67 45.83 50.00 54.17 58.33 62.50 66.67 70.83
l/sec or kg/s
0.14
0.21
0.28
0.35
0.42
0.49
0.56
0.63
0.69
0.76
0.83
0.90
0.97
1.04
1.11
1.18
2 - Velocity in pipe (limited to 1 m/s maximum) for pipe sizing
m/s in 22mm
0.37
0.55
0.73
0.91
-
-
-
-
-
-
-
-
-
-
-
-
m/s in 28mm
0.23
0.34
0.45
0.56
0.68
0.79
0.90
-
-
-
-
-
-
-
-
-
m/s in 35mm
0.14
0.22
0.29
0.36
0.43
0.51
0.58
0.65
0.72
0.79
0.87
0.94
-
-
-
-
m/s in 42mm
0.10
0.15
0.20
0.25
0.30
0.35
0.40
0.45
0.50
0.55
0.60
0.65
0.70
0.75
0.80
0.85
3 - Operating power of heat exchanger suitable for cylinder based on a 5 degree temperature difference
kW @ 5K dt
3-4
4-6
5.5-8
7-10
8-12
10-14 11-16 13-18 14-20 16-22 17-24 18-26 20-28 21-30 23-32 24-34
180HP
-
-
-
-
-
-
-
-
-
-
180HP + Sol
-
-
-
-
-
-
210HP
-
-
-
-
-
-
-
-
-
210HP + Sol
-
-
-
-
-
250HP
-
-
-
-
-
-
-
-
-
250HP + Sol
-
-
-
-
-
300HP
-
-
-
-
-
300HP + Sol
-
400HP
-
-
-
-
-
400HP + Sol
-
4 - Pressure loss (bar) for each fl ow rate above in the available coil combinations
180HP
0.010 0.027 0.053 0.092 0.143 0.207 0.286 0.381 0.491 0.618 0.763 0.927 1.109 1.310 1.532 1.774
180HP + Sol
0.003 0.008 0.017 0.031 0.049 0.073 0.103 0.140 0.183 0.234 0.292 0.359 0.434 0.518 0.612 0.715
210HP
0.017 0.040 0.074 0.118 0.173 0.239 0.316 0.405 0.505 0.617 0.741 0.877 1.025 1.184 1.356 1.540
210HP + Sol
0.013 0.033 0.064 0.107 0.164 0.234 0.318 0.417 0.532 0.663 0.810 0.975 1.156 1.356 1.574 1.810
250HP
0.006 0.015 0.028 0.045 0.067 0.093 0.124 0.159 0.200 0.245 0.295 0.350 0.410 0.475 0.545 0.620
250HP + Sol
0.004 0.011 0.021 0.036 0.054 0.077 0.105 0.138 0.176 0.218 0.267 0.321 0.380 0.445 0.517 0.594
300HP
0.008 0.019 0.036 0.058 0.086 0.120 0.160 0.206 0.259 0.318 0.384 0.457 0.536 0.623 0.716 0.816
300HP + Sol
0.004 0.014 0.031 0.058 0.098 0.152 0.223 0.312 0.421 0.553 0.708 0.890 1.100 1.339 1.610 1.915
400HP
0.004 0.010 0.018 0.030 0.044 0.062 0.083 0.108 0.136 0.167 0.202 0.241 0.283 0.329 0.379 0.432
400HP + Sol
0.008 0.018 0.031 0.049 0.070 0.094 0.123 0.155 0.190 0.230 0.273 0.319 0.370 0.423 0.481 0.542
INSTALLATION
Section 3 shows the maximum operating power
of the coils in the cylinder. Shaded squares show
the range of operating powers suitable for a
cylinder in either of its set ups.
Section 4 shows the pressure loss across the
coils at this fl ow rate for all cylinders in both
confi gurations.
Содержание StainlessLite HP180IND
Страница 17: ...Page 17 INSTALLATION INSTALLATION ...
Страница 26: ...Page 26 BENCHMARK ...
Страница 27: ...Page 27 BENCHMARK ...
Страница 28: ...Page 28 NOTES ...
Страница 29: ...Page 29 NOTES ...