Earthing the luminaire
The luminaire must be earthed in the terminal block. It can also be
earthed external, to the contact on the luminaire house. Shielded
cable must be earthed as described in the drawing.
Connection of GRX3 LED IC to the mains
When the GRX3 LED IC is connected to other luminaires as shows in the diagrams, the switch will switch
off/on all the luminaires. The light in all LED modules of the GRX3 LED IC can be switched while the bat-
tery will be charged uninterruptedly.
• Wiring without switch for main light
• Wiring with 1-poled switch for main light
Mains
L
N
L4
3
N
L1
2
L4
3
N
L1
2
GRX3 LED IC-E
Emergency
L4
3
N
L1
2
GRX3 LED IC
Not emergency
GRX3 LED IC-E
Emergency
Connection of GRX3 LED IC
L1 - N for not emergency (main light)
L4 - N for emergency (charging)
Power supply must be from same line (fuse) for both normal light and emergency.
Mains
L
N
L4
3
N
L1
2
L4
3
N
L1
2
L4
3
N
L1
2
GRX3 LED IC-E
Emergency
GRX3 LED IC
Not emergency
GRX3 LED IC-E
Emergency
Tereminal block
Torque value for screws: 1.8Nm
Type and size of wires that can be used:
Solid wire: From 1.0mm² to 6.0mm²
Stranded wire with or without ferrule: From 0.75mm² to 6.0mm²
There can only be connected one wire on each side of the screw on each
side of each terminal. (totally max 4 wires at each terminal).
7
Installation and operation GRX3 LED IC