Transmit reactive power

On, Off
Basic setting: On

Sends the current
fundamental oscillation idle
power value. If negative
values are displayed, this is
capacitive reactive power.
Positive values show an
inductive reactive power. 

Transmit apparent power

On, Off
Basic setting: On

Transmits the current
apparent output value.

Transmit absolute active
energy

On, Off
Basic setting: On

Transmits the cumulative
value of the active energy. If
negative values are displayed,
then effective energy is fed in,
e.g. via a photovoltaic system. 

Transmission interval

1 … 60 min
Basic setting: 15 min

The current consumption data
is transmitted at the interval
set here at the latest. Changes
to the effective power cause
fresh transmission, however
only after one minute at the
earliest. 

Rel. threshold value, effective
power 

1 ... 50 %
Basic setting: 10 %

The transmission of the
consumption data can be
coupled to the change in
effective power. The basis is
always the most recently
transmitted effective output
value. If the percentage
change entered here is
exceeded, then all the
measured values are resent.

Abs. threshold value, effective
power 

0 … 2000 W
Basic setting: 1 W

A lower threshold value of the
effective power can be
entered here, to avoid
frequent transmission in the
lower power range. Event-
controlled transmission is only
active above this threshold
value.

Suppression length, effective
power 

0 ms … 300 s
Basic setting: 0 ms

Triggers for event-controlled
transmission are often switch-
on and switch-off operations.
In order to avoid incorrect
measured values due to
switch-on peaks, this
parameter can be used to
enter a suppression period.
The measured values are only
transmitted if the effective
power is still above or below
the relative threshold value
after the set time. 

Averaging length

0.2 … 300 s
Basic setting: 1 s

In the case of effective power,
it is not the current value
which is transmitted, as with
other measured values, but
the average value. It is
possible to set the period for
average value formation here.

32581512

10864964

11.04.2017

6/8

Wireless energy sensor, 1-gang Mini

Содержание 5471 00

Страница 1: ...vice components Figure 1 Energy sensor 1 Status LED red 2 Button Prog 3 Terminals 3 Function Intended use Energy sensor for radio transmission of voltage current and energy values Operation with eNet server Mounting in appliance box according to DIN 49073 with a suitable cover Mounting in surface mounted housing or built in housing accessory for false ceilings i The energy sensor is not officially...

Страница 2: ...at least one minute Default setting Time controlled transmission transmission interval 15 minutes Event controlled transmission Rel threshold value effective power 10 Abs threshold value effective power 1 W Transferred characteristic electric values Current Voltage Average effective power Interval for average formation configurable between 0 2 300 s Apparent power Fundamental oscillation idle powe...

Страница 3: ...e commissioning interface of the eNet server Create or open the project into which the energy sensor is to be integrated see product documentation of the eNet server o Start the device search in the commissioning interface of the eNet Server o Press button Prog 2 for longer than 4 seconds The status LED 4 flashes after 1 seconds The energy sensor is in programming mode for approx 1 minute The eNet...

Страница 4: ... sleeve 0 75 2 5 mm Dimensions Ø H 53 23 mm Radio frequency 868 0 868 6 MHz Transmission capacity max 20 mW Transmitting range in free field typ 100 m Measuring ranges Current 0 mA 16 A Accuracy current 0 5 of the current value and 8 mA Voltage 207 250 V Accuracy voltage 0 5 of curr val Transmitted power and output values Effective output 4000 4000 W Apparent output 0 4000 VA Idle output 4000 4000...

Страница 5: ...s Parameters Setting options Basic setting Explanations Active energy 1073741823 1073741823 Wh Basic setting 0 Wh Current value Displays the currently cumulated active energy The value can be reset to 0 or set to any other value Extended channel settings Parameters Setting options Basic setting Explanations Manual commissioning On Off Basic setting On Blocks manual commissioning for the device cha...

Страница 6: ...he most recently transmitted effective output value If the percentage change entered here is exceeded then all the measured values are resent Abs threshold value effective power 0 2000 W Basic setting 1 W A lower threshold value of the effective power can be entered here to avoid frequent transmission in the lower power range Event controlled transmission is only active above this threshold value ...

Страница 7: ...source e g a photovoltaic system feeding in energy Cause 2 The energy sensor is connected in reverse polarity Connect the energy sensor with the correct polarity i If negative reactive power values are displayed this is a capacitive idle power Positive values show an inductive reactive power 5 4 Accessories Installation adapter Mini housing Order No 5429 00 eNet Server Order No 5301 00 5 5 Conform...

Страница 8: ... Systeme Industriegebiet Mermbach Dahlienstraße 42477 Radevormwald Postfach 12 20 42461 Radevormwald Deutschland Tel 49 0 21 95 602 0 Fax 49 0 21 95 602 191 www gira de info gira de 32581512 10864964 11 04 2017 8 8 Wireless energy sensor 1 gang Mini ...

Отзывы: