Resetting the device to the factory setting
The connection to the eNet server is disconnected and parameters are reset to default setting.
o
Press the
Prog
button for at least 20 seconds.
The status LED flashes after 4 seconds. After 20 seconds the status LED flashes faster.
o
Release
Prog
button and press briefly once again within 10 seconds.
The status LED flashes more slowly for approx. 5 seconds.
Device is reset to default setting.
5 Appendix
5.1 Technical data
Rated voltage
AC 230 V ~
Mains frequency
50 / 60 Hz
Rated load current
16 A (I
L
)
Peak current (1 s)
80 A
Peak current (1 min)
24 A
Power consumption
max. 0.5 W
Transmission interval
1 ... 60 min
Ambient temperature
-25 ... +70 °C
Connection
single stranded
0.75 ... 4 mm²
Finely stranded with conductor sleeve
0.75 ... 2.5 mm²
Dimensions Ø×H
53×23 mm
Radio frequency
868.0 ... 868.6 MHz
Transmission capacity
max. 20 mW
Transmitting range in free field
typ. 100 m
Measuring ranges
Current
0 mA ... 16 A
Accuracy (current)
± 0.5 % of the current value and ± 8 mA
Voltage
207 ... 250 V
Accuracy (voltage)
± 0.5 % of curr. val.
Transmitted power and output values
Effective output
-4000 ... 4000 W
Apparent output
0 ... 4000 VA
Idle output
-4000 ... 4000 var
Accuracy (power)
± 0.5 % of the current value and ± 2 W/VA/var
Effective energy
-99999 ... 99999 kW·h
Receiver category
2
5.2 Parameter list
The device parameters can be changed with the eNet server:
Device and channels
Parameters
Setting options, Basic
setting
Explanations
Function
Energy, Unused
Basic setting: Energy
Energy
The channel works as an
energy sensor.
Unused
The channel is not displayed
in the
eNet SMART HOME
app
and is disabled for use in
the commissioning interface.
32581512
10864964
11.04.2017
4/8
Wireless energy sensor, 1-gang Mini