background image

Wireless energy sensor, 1-gang Mini

Order No. : 5471 00

Operating instructions

1 Safety instructions

Electrical devices may only be mounted and connected by electrically skilled
persons.

Serious injuries, fire or property damage possible. Please read and follow manual fully.

Danger of electric shock. Always disconnect before carrying out work on the devise or
load. In so doing, take all the circuit breakers into account, which support dangerous
voltages to the device and or load.

These instructions are an integral part of the product, and must remain with the end
customer.

2 Device components

Figure 1: Energy sensor

(1) Status LED, red 
(2) Button 

Prog

(3) Terminals

3 Function

Intended use

-

Energy sensor for radio transmission of voltage, current and energy values

-

Operation with eNet server

-

Mounting in appliance box according to DIN 49073 with a suitable cover

-

Mounting in surface-mounted housing or built-in housing (accessory) for false ceilings

i

The energy sensor is not officially calibrated and may not therefore be used for invoicing
purposes.

Product characteristics

-

Detection of current and voltage of the connected consumer

-

Calculation of the effective, idle, apparent power and the active energy

-

Event or time-controlled transmission of measured value telegrams to the eNet server

1/8

32581512

11.04.2017

Wireless energy sensor, 1-gang Mini

10864964

Содержание 5471 00

Страница 1: ...vice components Figure 1 Energy sensor 1 Status LED red 2 Button Prog 3 Terminals 3 Function Intended use Energy sensor for radio transmission of voltage current and energy values Operation with eNet server Mounting in appliance box according to DIN 49073 with a suitable cover Mounting in surface mounted housing or built in housing accessory for false ceilings i The energy sensor is not officially...

Страница 2: ...at least one minute Default setting Time controlled transmission transmission interval 15 minutes Event controlled transmission Rel threshold value effective power 10 Abs threshold value effective power 1 W Transferred characteristic electric values Current Voltage Average effective power Interval for average formation configurable between 0 2 300 s Apparent power Fundamental oscillation idle powe...

Страница 3: ...e commissioning interface of the eNet server Create or open the project into which the energy sensor is to be integrated see product documentation of the eNet server o Start the device search in the commissioning interface of the eNet Server o Press button Prog 2 for longer than 4 seconds The status LED 4 flashes after 1 seconds The energy sensor is in programming mode for approx 1 minute The eNet...

Страница 4: ... sleeve 0 75 2 5 mm Dimensions Ø H 53 23 mm Radio frequency 868 0 868 6 MHz Transmission capacity max 20 mW Transmitting range in free field typ 100 m Measuring ranges Current 0 mA 16 A Accuracy current 0 5 of the current value and 8 mA Voltage 207 250 V Accuracy voltage 0 5 of curr val Transmitted power and output values Effective output 4000 4000 W Apparent output 0 4000 VA Idle output 4000 4000...

Страница 5: ...s Parameters Setting options Basic setting Explanations Active energy 1073741823 1073741823 Wh Basic setting 0 Wh Current value Displays the currently cumulated active energy The value can be reset to 0 or set to any other value Extended channel settings Parameters Setting options Basic setting Explanations Manual commissioning On Off Basic setting On Blocks manual commissioning for the device cha...

Страница 6: ...he most recently transmitted effective output value If the percentage change entered here is exceeded then all the measured values are resent Abs threshold value effective power 0 2000 W Basic setting 1 W A lower threshold value of the effective power can be entered here to avoid frequent transmission in the lower power range Event controlled transmission is only active above this threshold value ...

Страница 7: ...source e g a photovoltaic system feeding in energy Cause 2 The energy sensor is connected in reverse polarity Connect the energy sensor with the correct polarity i If negative reactive power values are displayed this is a capacitive idle power Positive values show an inductive reactive power 5 4 Accessories Installation adapter Mini housing Order No 5429 00 eNet Server Order No 5301 00 5 5 Conform...

Страница 8: ... Systeme Industriegebiet Mermbach Dahlienstraße 42477 Radevormwald Postfach 12 20 42461 Radevormwald Deutschland Tel 49 0 21 95 602 0 Fax 49 0 21 95 602 191 www gira de info gira de 32581512 10864964 11 04 2017 8 8 Wireless energy sensor 1 gang Mini ...

Отзывы: