background image

System 3000

Electronic switching insert

Electronic switching insert
Order no.: 5405 00

Operating instructions

1

Safety instructions

Electrical devices may only be mounted and connected by electrically skilled persons.

Serious injuries, fire or property damage possible. Please read and follow manual fully.

Danger of electric shock. Always disconnect before carrying out work on the devise or load.

Danger of electric shock. Device is not suitable for disconnection from supply voltage. The load
is not electrically isolated from the mains even when the device is switched off.

Risk of destruction if the set operating mode and load type do not match. Set correct operating
mode when connecting or exchanging the load.

Fire hazard. For operation with inductive transformers, each transformer must be fused on the
primary side in accordance with the manufacturer's instructions. Only safety transformers ac-
cording to EN 61558-2-6 may be used.

These instructions are an integral part of the product, and must remain with the end customer.

2

Intended use

Operation with suitable cover

Mounting in appliance box according to DIN 49073

Operation with neutral conductor

Switching of incandescent lamps, HV halogen lamps, electronic or inductive transformers
with halogen or LED lamps, switchable or dimmable HV-LED or compact fluorescent
lamps, electrothermal actuators in combination with room temperature controller covers

Operation without neutral conductor

Switching of incandescent lamps, HV halogen lamps, electronic or inductive transformers
with halogen or LED lamps, dimmable HV-LED or compact fluorescent lamps

Product characteristics

Switch-on via bulb-preserving soft start

Connection of extensions possible

Electronic short-circuit protection with permanent switch-off after 7 seconds at the latest

Electronic over-temperature protection

Flickering of the connected lamps through centralised pulses from the power stations.
This does not represent any defect in the device.

Operation with neutral conductor

Device is powered via phase conductor and neutral conductor , therefore there is no lead-
ing edge phase control or trailing edge phase control.

Operation without neutral conductor

Device is powered via the phase conductor and the connected load and therefore works
in the leading edge phase control or trailing edge phase control principle

Automatic or manual setting of the suitable operating mode for the load

Display of the set operating mode by means LED

Brief flickering upon load detection possible. No operation is possible during load detec-
tion.

1 / 7

82400512

24.05.2019

Содержание 5405 00

Страница 1: ...halogen lamps electronic or inductive transformers with halogen or LED lamps switchable or dimmable HV LED or compact fluorescent lamps electrothermal actuators in combination with room temperature c...

Страница 2: ...on the main device Switch load Press the button cover The load is switched on or off 3 wire extension Press top to switch on press bottom to switch off 4 Information for electrically skilled persons...

Страница 3: ...c overheating or short circuit protection has been activated separate the switch insert from the grid for a few minutes 4 2 Commissioning Operation with neutral conductor The device is powered via the...

Страница 4: ...oad is switched off Press button Test 1 for longer than 4 seconds until LED 2 lights up Figure 3 Assignment of LED colour for the operating mode Keep pressing button Test 1 for less than 1 second unti...

Страница 5: ...rotary dimmer extension 10 Total line length Extension max 100 m pwr cable max 100 m 6 Troubleshooting Connected lamps flicker Cause the specified minimum load is below the set level Increase the conn...

Страница 6: ...ation of the operational current Cause 4 load failure Check load replace light bulb For inductive transformers check primary fuse LED lamp is dimly lit when device is switched off Cause LED lamp is no...

Страница 7: ...ersiepen GmbH Co KG Elektro Installations Systeme Industriegebiet Mermbach Dahlienstra e 42477 Radevormwald Postfach 12 20 42461 Radevormwald Deutschland Tel 49 0 21 95 602 0 Fax 49 0 21 95 602 191 ww...

Отзывы: