System 3000
Electronic switching insert
Mixed load
ohmic-capacitive
20 ... 400 W
capacitive-inductive
not permitted
ohmic-inductive
20 ... 400 VA
Ohmic and HV LED
typ. 3 ... 100 W
Ohmic and compact fl lamp.
typ. 3 ... 100 W
Power specifications including transformer dissipation.
Operate inductive transformers with at least 85% nominal load.
Operation without neutral conductor in operating mode R,L,C,LED: Ohmic-inductive
mixed load: maximum 50% proportion of ohmic load. Otherwise, an incorrect measure-
ment is possible.
Operation without neutral conductor: Minimum load 50 W. Does not apply to loads with
HV-LED and compact fluorescent lamps.
Power reduction
per 5°C in excess of 25°C
-10%
when installed in wooden or dry construction walls
-15%
when installed in multiple combinations
-20%
electrothermal actuators order no.: 2169 00
Number
1 ... 10
Number of extension units
2-wire, push-button
unlimited
3-wire, rotary dimmer extension
10
Total line length
Extension
max. 100 m
pwr cable
max. 100 m
6
Troubleshooting
Connected lamps flicker
Cause: the specified minimum load is below the set level.
Increase the connected load.
Connected LED lamps or compact fluorescent lamps flicker or buzz, device buzzes
Cause 1: lamps are not dimmable and device is connected without neutral conductor
Connect neutral conductor if possible, otherwise exchange lamps for dimmable lamps.
Cause 2: operating mode and lamps do not optimally match.
Check operation in another operating mode, reduce connected load as well if necessary.
Set the operating mode manually.
Exchange lamps for another type.
The device switches the load off briefly and then on again.
Cause: short-circuit protection has tripped but now there is no longer a fault.
The device has switched off and cannot be switched on again.
Cause 1: overheating protection has tripped.
Disconnect device from mains by switching off circuit breaker.
LED trailing edge phase control: Reduce the connected load. Exchange lamps for another
type.
5 / 7
82400512