c. All surfaces on the GigaVUE TA Series-TA10, GigaVUE TA Series-TA40, GigaVUE
TA Series-TA100, or GigaVUE TA Series-TA200 that are unplated shall be
brought to a bright finish and treated with an antioxidant solution before
connections are made.
d. All non-conductive surfaces on the GigaVUE TA Series-TA10, GigaVUE TA Series-
TA40, GigaVUE TA Series-TA100, or GigaVUE TA Series-TA200 shall be removed
from all threads and connection points to ensure electrical continuity.
e. Multiple connectors shall not be secured by the same bolt assemblies.
f. Unplated connection surfaces that are to be intentionally joined to form a
bonding or grounding path shall be brought to a bright finish and then coated
with an antioxidant before they are joined (electrical connections).
g. Listing fasting hardware shall be compatible with materials being joined and
shall preclude loosening deterioration, and electrochemical corrosion of the
hardware and joined materials.
h. Non-conductive coatings (such as paint, lacquer, and enamel) on the equipment
to be bonded or grounded shall be removed from threads and other contact
surfaces to assure electrical continuity.
i. GigaVUE TA Series-TA10, GigaVUE TA Series-TA40, GigaVUE TA Series-TA100, or
GigaVUE TA Series-TA200 utilizes a Spade width 0.32in/.81cm with a Standard
Wire 14-16 (AWG) that utilizes 5in-lbs of torque to secure it to the frame and EUT.
Only listed two-hole compression-type connectors shall be used in making
connection to flat surfaces (such as bus bars, frames, racks, or cabinets).
Torquing and bolts assembly requirements for securing the connector shall be
as specified by the connector supplier.
j. Anti-rotation devices, such as lock washers, will be used on grounding lugs to
minimize the possibility of loosening from rotation during installation and
maintenance activities.
Input AC/DC Voltage
The GigaVUE TA Series-TA10, GigaVUE TA Series-TA40, GigaVUE TA Series-TA100, and
GigaVUE TA Series-TA200 is capable of operating input 100-240V AC or -48V DC.
Commercial Power Ports
The manufacturer recommends that Surge Protection Device (SPD) is intended to be
used with AC-power equipment. The SPD, if used, is installed at the AC power entrance
(Refer to definition in the NEC).
Contents
108
GigaVUE TA Series Hardware Installation Guide