GiBiDi DPT260 Скачать руководство пользователя страница 12

12

DPT260

1.

Dig an excavation of about mm 1000 x 1000 section and of 1200mm depth 

(PIC. 1)

.

2. 

Ensure that the soil has a good permeability (read the specific procedure at chapter 5.2).

NOTE:

 it is recommended to read chapter 5.1 “tests before installation”.

3. 

Add gravel for approx. 300mm (grain diameter from 8mm to 20mm approx.), make sure to vibrate and to 
compact it accurately to avoid any future ground settling 

(PIC. 2)

.

4.

  Lay the metallic pit equipped with counterframe and brackets, paying attention to:

 

• Arrange the pits according to the transit direction as indicated on the counterframe 

(PIC. 5)

.

 

• Check that the pits are correctly plumbed

 (PIC. 2)

.

 

• Ensure that the counterframe is 10mm higher than walking level (in order to limit rainwater infiltrations into the  
   pit). To arrange the pit at the suitable height, add or remove gravel under the pit 

(PIC. 3)

.

5.

In case of installation with multiple pits, ensure that they are all well alligned and oriented in the same direction 

(PIC. 6)

.

6.

Add gravel all around the pit for about 200mm to avoid any obstruction of the drainage holes, placed at the 
bottom of the pit, during the concrete casting.

7. 

Lay a flexible sheath of 50mm diameter from each pit to the control unit for the electrical connection of the 
bollards 

(PIC. 2 and 4

).

WARNING!

If the distance between pits and control unit is more than 10m, purchase the bollards equipped 
with electrical connection lines of the suitable length (standard length 10m – optional: up to  80m).

8.

  In case an “immersion pump” is needed (as described in chapter 5.2), lay a 50mm diameter sheath from the “pit 

for rainwater collection” to the control unit and connect the drainage pipe to the sewer system or similar. Take 
into account the installation of a non-return valve or similar, to avoid any flow back into the pit.

9. 

Arrange correctly the brackets supplied with the pits 

(PIC. 4)

.

10.

Cast concrete all around the pits until 100mm under the walking level (evaluate this quota according to the type 
of road surface).

NOTE: 

 it is recommended to cast concrete in two steps to avoid the lifting of the pits due to flotation in liquid 

   concrete. It is also recommended to vibrate the concrete to compact it properly.

11.

  Lay any additional pipe from the control unit to the installation point of the accessories (i.e. inductive loops, traffic 

lights, consolle, etc.). Prearrange the electrical connection and the earthing to the control unit.

12. 

Once the concrete has solified, carry out the road surface finish.

All the pipelines shall be laid in full compliance with the regulations in force.

5.3 - LAYING OF THE PIT

UK

Содержание DPT260

Страница 1: ...DPT260 DPT260 UK Automatic bollards FITTING OPERATION AND MAINTENANCE INSTRUCTIONS...

Страница 2: ...ed anti flame cable The dimension of the main power supply line must be evaluated by the installeraccordingtothequantityofbollards 500Weachbollard andthedistancefromtheoutputplace inorderto grantaprop...

Страница 3: ...g effects in a range between 25 C and 55 C and foradeterminedtime lessthan24hours at 70 C The bollards do not require any availability of spare parts Gi Bi Di S r l warehouse can send any spare parts...

Страница 4: ...s Lowering speed 25 cm s Manual emergency lowering Standard optional automatic lowering if power failed Safety reversal pressure switch Standard Connection line to control unit Standard 10 m max lengh...

Страница 5: ...4 BOLLARD COMPONENTS 40 600 275 940 560 560 SOLENOID VALVE RISING SIDEBLOCK LOWER LIMIT SWITCH LOWER SUPPORT BASE REFLECTING STRIP FLASHING LIGHT HEAD MOVING CYLINDER FRAME PASSIVE BOX PISTON HYDRAULI...

Страница 6: ...6 DPT260 5 INSTALLATION PROCEDURE 190 mm 200 mm 300 mm 1200 mm 1000 mm 1000 mm Quota di calpestio 10 mm SENSO DI TRAFFICO TRAFFIC WAY 50 mm PIC 1 PIC 2 PIC 3 PIC 5 PIC 4 UK...

Страница 7: ...7 DPT260 5 INSTALLATION PROCEDURE UK PIC 6 FOUNDATION BRACKET CONTROL UNIT JUNCTION BOX 400 x 400 mm FLEXIBLE SHEATH diameter 50 mm max 1600 mm max 1600 mm...

Страница 8: ...S WALKING LEVEL ROAD SURFACE ADDITIONAL CONCRETE CASTING SUPPORTING SLAB M8 CHEMICAL ANCHORS M16 CHEMICAL ANCHORS WATERPROOF PIT IN STAINLESS STEEL WATERPROOFING SHEATH 10 mm 50 mm 600 mm 275 mm 450 m...

Страница 9: ...9 DPT260 PIC 8 PIC 10 PIC 11 PIC 9 M16 M16 5 INSTALLATION PROCEDURE UK...

Страница 10: ...10 DPT260 5 INSTALLATION PROCEDURE min 25 cm 95 cm 95 cm 95 cm 95 cm 3 00 m 1 80 m 280 cm 200 cm 80 cm 80 cm 5 5 cm 9 cm 15 cm 15 cm 15 cm PIC 12 PIC 14 PIC 16 PIC 13 PIC 15 PIC 17 Control Unit UK...

Страница 11: ...annel complete with covering grid to avoid rainwater infilitrations in the pits due to incline An important factor in the installation of bollards prior to the assessment of the permeability of soil i...

Страница 12: ...it to the control unit for the electrical connection of the bollards PIC 2and4 WARNING If the distance between pits and control unit is more than 10m purchase the bollards equipped withelectricalconne...

Страница 13: ...e the stainless steel waterproof pits to the ceilingofthebasement 7 Laythepipesfortheelectricalcablesfromthebollardstothecontrolunit 8 Laythepipesforrainwaterdrainagefromthewaterproofpitstothedrainage...

Страница 14: ...ke into account other dimensions 2 The inductive loop is made of a special cable of 9mm diameter and it is suitable for the direct laying into the ground withoutanysheathnorprotection 3 Itisessentialt...

Страница 15: ...G No 1 2 3 4 5 6 Colour BLUE GREY YELLOW BLACK WHITE RED Device FLASHING LIGHT BUZZER optional SOLENOID VALVE FOR LOWERING SAFETY PRESSURE SWITCH LIMIT SWITCH BOLLARD DOWN LIMIT SWITCH BOLLARD UP opti...

Страница 16: ...ting bollard downposition Grey Sensor for detecting bollard up position nc Red Solenoid valve 24Vdc 1 3 2 4 2 4 2 4 4 2 1 1 2 4 2 6 BROWN 5 WHITE 3 YELLOW 1 BLUE 2 GREY Hydraulicl unit 4 BLACK M12 1 3...

Страница 17: ...5bollards i e controlunitfor8bollards Electronic circuit Standard housing for control unit Protection class Power supply Control unit protection Service transformer Permitted ambient temperature Relat...

Страница 18: ...everysinglebollard 5 Layandconnectanyadditionallines e g push buttonpanel inductiveloops trafficlights etc 6 Before running a functional test consult the instructions related to the electric connectio...

Страница 19: ...parameters of the system 230V 10 per each moving bollard Master Slave F1 F2 F3 F5 F1 F6 F7 F2 Typology Protection 2A delayed Protection transformer 230V 24 VAC supply 1A delayed Protection timer progr...

Страница 20: ...t outlet for yearly weekly progremmer connection Outlet 230V power supply for hydraulic pump common terminal 8 L7 L3 L4 L1 L2 L13 L13 LIN L5 L12 L11 L14 Outlet 24V power supply for solenoid valve Outl...

Страница 21: ...Step Step Outlet for hydraulic pump power supply rising Outlet for hydraulic pump power supply lowering Outlet for hydraulic pump power supply in motion Inlet for safety devices Rising phase disabled...

Страница 22: ...ne None Outlet 230V power supply for hydraulic pump common terminal 8 L7 L3 L4 L1 L2 Outlet 24V power supply for solenoid valve Outlet 24V power supply for acoustic buzzer Outlet 24V power supply for...

Страница 23: ...ts rising lowering Power supply enabled Power supply enabled Limit switch enabled device in low position gate open Outlet enabled fixed or flashing depending on setting Outlet enabled fixed or flashin...

Страница 24: ...STEPFUNCTION The bollard after the first control from up position moves to down position after another control the bollardreturnstoupposition step stepfunction CONTROLSENABLED Controlsfortheoperationo...

Страница 25: ...pressed until the completeloweringofthebollard 4 Fastenthedowel PIC 23andPIC 24 PIC 25 PIC 26 PRESSURE SWITCHAS RISING LIMIT SWITCH ENABLED At the final stage of the rising the pressure switch worksas...

Страница 26: ...a bollard during the rising phase the safety pressure switch detects the presence of a weight and immediately interrupts the rising phase and makes the bollards lower to down position inversion contr...

Страница 27: ...upt the rising phase and make bollardsgobacktodownposition inversioncontrolbyinductiveloop Wetherthissituationoccurs beforecrossingit isnecessarytowaitforthegreensectortoturn If a pedestrian steps on...

Страница 28: ...levant during winter they can be equipped with an heating resistance which prevents ice formation between the cylinder and the fixed side crown allowingfortheproperoperationofthesystem If automatic bo...

Страница 29: ...icted or blocked In order to keep an adeguate drainage use a drill machine of suitable length approx 15mm anddrillinthe4holes drivingthetipintothegravelbelowforabout10cm Inthiswayanydepositthatobstruc...

Страница 30: ...is rising and the pressure switch detects a pressure increase usually caused by the detection of a weight corresponding to 40 kg or more on the bollard e g a person the bollard stops and goes back to...

Страница 31: ...and transmitters check the correct operation from a distance of about 30m and as far as possible verify the wear of thetransmittersandthebuilt inbatteries Check visually the overall status of the cont...

Страница 32: ...ghthesuitablespyhole Unfasten and remove the black cap of the hydraulic pump generally placed abovethetransparentspyhole andfillitwiththesameoiluptoabouthalfofthe spyhole ATTENTION USEORIGINALOILONLY...

Страница 33: ...ed thisblackwirepowersthefirstpointat 24VDC Move the black wire from the first terminal to the second or the third one to poweranotherlightpoint Test the proper operation of the multiled flashing ligh...

Страница 34: ...ocedurebelow Bollardoutofthepit Bollardindownposition turn230Vpowersupplyoff Extract the waterproof protection made of black soft rubber for about 5cm toreachtheadjustingscrew Unscrew and remove the n...

Страница 35: ...of 45 and after each step command a rising movement Once the bollard is completely up check the pressure on the pressure gauge and most important hear that the hydarulic unit continues running for abo...

Страница 36: ...orreplaced For the pressure switch adjustment please consult the chapter10 SPECIFICOPERATIONS Note generally only the pressure switches of old supply are adjustable and recognizable from a waterproof...

Страница 37: ...n reversalfunctionbypressureswitchenabled If it is possible adjust the pressure switch sensibility adjustable old version or replace the pressure switch pre adjusted and hermetic new version to increa...

Страница 38: ...n it is lower than a certain value it performs an automatic adjustment When it occurs this problemmaybecausedby The automatic pressure adjust ment has been accidentally excluded The safety inductive d...

Страница 39: ...board Consult the chapter 10 SPECIFICOPERATIONS UK EC Declaration of conformity The manufacturer GI BI DI Via Abetone Brennero 177 B 46025 Poggio Rusco MN ITALY declares that the products AUTOMATIC B...

Страница 40: ...DI S r l Via Abetone Brennero 177 B 46025 Poggio Rusco MN ITALY Tel 39 0386 52 20 11 Fax 39 0386 52 20 31 E mail info gibidi com Numero Verde 800 290156 w w w g i b i d i c o m Cod AIC0061 01 2020 Re...

Отзывы: