41
GI-IM048En-1013
PART 7 – GAS CONNECTIONS
Failure to follow all precautions could result in fire, explosion, severe injury or death!
The gas supply shall have a maximum inlet pressure of less than 14"
water column (35.6 cm), ½ pound pressure (3.5 kPa), and a minimum of
3.5" water column (8.9 cm). The entire piping system, gas meter and
regulator must be sized properly to prevent pressure drop greater than
0.5" WC (1.3 cm) as stated in the National Fuel Gas Code. This
information is listed on the rating plate.
It is very important that you are connected to the type of gas as noted on
the rating plate: "LP" for liquefied petroleum, propane gas, or "Nat" for
natural or city gas. All gas connections must be approved by the local
gas supplier or utility, in addition to the governing authority, prior to
turning the gas supply on.
Do not remove the adaptor in
Figure
! It is mandatory that this fitting is
used for connection to a field fabricated drip leg per the National Fuel
Gas Code. You must ensure that the entire gas line to the connection at
the water heater is no smaller than ¾" (1.9 cm).
Once all inspections have been performed, the piping must be leak
tested. If the leak test requirement is a higher test pressure than the
maximum gas inlet pressure, you must isolate the heater from the gas
line to continue leak testing. To do this, you must turn off the factory and
field-installed gas cocks. This will minimize the possibility of damaging
the gas valve. Failure to do so may damage the gas valve. In the event
the gas valve is exposed to a pressure greater than ½ PSI, 14" water
column (35.6 cm), the gas valve must be replaced. Never use an open
flame (match, lighter, etc.) to check gas connections.
A. GAS PIPING
Run the gas supply line in accordance with all applicable codes. Locate
and install manual shutoff valves in accordance with local and state
requirements.
B. GAS TABLE
Refer to the table below to size the supply piping to minimize pressure
drop between meter or regulator and unit.
Maximum capacity of pipe in cubic feet of gas per hour for gas pressures
of .5 psi or less and a pressure drop of .3 inch water column (7.6 mm).
Nominal Iron
Pipe Size (In.)
Internal
Dia. (In.)
Length of Pipe (Feet)
BTU’s
Per
Hour x
1,000
10
20
30
40
50
60
70
80
90
100
125
150
175
200
¾
(1.9 cm)
.824
(2.1 cm)
278 190 152 130 115 105 96 90 84 79 72 64 59 55
1
(2.5 cm)
1.049
(2.7 cm)
520 350 285 245 215 195 180 170 160 150 130 120 110 100
1 ¼
(3.2 cm)
1.380
(3.5 cm)
1,050 730 590 500 440 400 370 350 320 305 275 250 225 210
1 ½
(3.8 cm)
1.610
(4.1 cm)
1,600 1,100 890 760 670 610 560 530 490 460 410 380 350 320
Table 10: Source- ANSI Z223.1
Figure 23: Phoenix Gas Connection - LP-179-Q
Содержание UGC120S-100
Страница 36: ...36 GI IM048En 1013 Figure 18 LP LP ...
Страница 39: ...39 GI IM048En 1013 D INTERNAL WIRING DIAGRAM Figure 21 Wiring Diagram LP ...
Страница 40: ...40 GI IM048En 1013 Figure 22 LP 179 L LP ...
Страница 49: ...49 GI IM048En 1013 Figure 26 LP 179 J LP ...
Страница 50: ...50 GI IM048En 1013 Figure 27 LP 179 H LP ...
Страница 52: ...52 GI IM048En 1013 MAINTENANCE NOTES ...