PART 6 – WIRING
A. LINE VOLTAGE INPUT
The heater must be wired to a 120 volt circuit by a qualified electrician. It is recommended that the heater be wired on its own circuit to
minimize the possibility of circuit failure due to outside causes. The heater requires a maximum of 8 amps at 120 volts in use.
B. LINE VOLTAGE CONDENSATE OUTPUT
The heater has the capability of supplying power to a condensate pump. The connection is 120 VAC +/- 10% at a max of 2 amps.
Power is supplied to the pump only when the heater is connected to power, and the power switch is in the on position.
C. LOW VOLTAGE OUTDOOR SENSOR INPUT
The heater has the capability of an outdoor reset. Connecting an outdoor sensor allows the heater to operate at optimum efficiency.
GIANT offers an outdoor sensor, p/n 7250P-319.
The outdoor sensor must be a 12K NTC sensor. Use a minimum 22 AWG wire for runs of 100 feet (30.5 m) or less and minimum 18
AWG wire for runs up to 150 feet (45.7 m). Instructions are included with the outdoor sensor to correctly mount the sensor on the
exterior surface of the building. It is preferable to mount the sensor on the north side in an area that will not be affected by direct
sunlight but will be exposed to varying weather conditions. Connect the outdoor sensor to terminals marked “Outdoor”.
Figure 20: Low Voltage Wiring
Label all wires prior to disconnecting them when servicing the heater. Wiring errors can cause improper and dangerous operation.
Failure to follow these instructions may result in property damage or personal injury.
To avoid electrical shock, turn off all power to the heater prior to opening an electrical box within the unit. Ensure the power remains off
while any wiring connections are being made. Failure to follow these instructions could result in component or product failure, serious
injury, or death. Such product failure IS NOT covered by warranty.
It is of extreme importance that this unit be properly grounded. It is very important that the building system ground is inspected by a
qualified electrician prior to making this connection. Electrical power must only be turned on when the heater is completely filled with cold
water.
Содержание UGC120S-100
Страница 36: ...36 GI IM048En 1013 Figure 18 LP LP ...
Страница 39: ...39 GI IM048En 1013 D INTERNAL WIRING DIAGRAM Figure 21 Wiring Diagram LP ...
Страница 40: ...40 GI IM048En 1013 Figure 22 LP 179 L LP ...
Страница 49: ...49 GI IM048En 1013 Figure 26 LP 179 J LP ...
Страница 50: ...50 GI IM048En 1013 Figure 27 LP 179 H LP ...
Страница 52: ...52 GI IM048En 1013 MAINTENANCE NOTES ...