The exhaust and intake components installed with this heater must be used for near heater piping BEFORE transitioning to the
approved materials listed above. DO NOT REMOVE these installed components. Doing so WILL VOID heater warranty.
PVC/CPVC pipe and fittings of the same diameter are considered interchangeable.
DO NOT use Foam Core Pipe in any portion of the exhaust piping from this water heater.
DO NOT connect PVC/CPVC to PP without an approved vent connector.
When installing AL29-4C vent piping, install a PVC-to-stainless adapter at the heater vent connection, and at the termination
when using an GIANT PVC termination kit. DO NOT mix AL-29-4C piping from different manufacturers unless using adapters
specifically designed for the purpose by the manufacturer.
*PVC-DWV for air intake applications ONLY.
Failure to follow these directions will result in substantial property damage, severe personal injury, or death.
DO NOT mix components from different venting systems. The vent system could fail, causing leakage of flue products into the living
space. Use only the approved pipe and fitting materials, and primer and cement specifically designed for the material used, as listed in
Table 4. Failure to do so could result in property damage, severe personal injury, or death.
Exhaust vent adaptors are not designed as load-bearing devices, and must not be used to support exhaust vent piping. All vent pipes
must be properly connected, supported, and the exhaust must be pitched a minimum of ¼” (6.3 mm) per foot back to the heater to allow
drainage of condensate. Failure to properly support vent piping and follow the information in this statement could result in product
damage, severe personal injury, or death.
NOTE:
The use of double-wall vent or insulated material for the combustion air inlet pipe is recommended in cold climates to prevent
the condensation of airborne moisture in the incoming combustion air.
C. REQUIREMENTS FOR INSTALLATION IN CANADA
1. Installations must be made with a vent pipe system certified to ULC-S636. IPEX is an approved vent manufacturer in Canada
supplying vent material listed to ULC-S636. Additionally you may use AL29-4C stainless steel venting to comply with Canadian
requirements.
2. The first three (3) feet (91 cm) of vent pipe from the water heater flue outlet must be readily accessible for visual inspection.
3. The components of the certified vent system must not be interchanged
with other vent systems or unlisted pipe / fittings.
Cellular foam core piping may be used on air inlet piping
only
.
You must not use “B” vent in an exhaust application. “B” vent is for intake
applications
ONLY
. Using “B” vent in an exhaust application will result in
serious injury or death.
D. EXHAUST VENT AND INTAKE PIPE LOCATION
1. DETERMINE EXHAUST VENT LOCATION
a. The vent piping for this water heater is approved for zero
clearance to combustible construction.
b. See illustration within this section of clearances for location of
exit terminals of direct-vent venting systems.
c. This water heater vent system shall terminate at least three (3)
feet (91 cm) above any forced air intake located within ten (10)
feet (3 m). Note: this does not apply to the combustion air intake of
a direct-vent appliance.
d. Provide a minimum of one (1) foot (30 cm) distance from any door, operable window, or gravity intake into any building.
e. Provide a minimum of one (1) foot (30 cm) clearance from the bottom of the exhaust above the expected snow
accumulation level. Snow removal may be necessary to maintain clearance.
f. Provide four (4) feet (1.2 m) horizontal clearance from electrical meters, gas meters, gas regulators, relief equipment,
exhaust fans and inlets. In no case shall the exit terminal be above or below the aforementioned equipment unless the four (4)
feet (1.2 m) horizontal distance is maintained.
Содержание UGC120S-100
Страница 36: ...36 GI IM048En 1013 Figure 18 LP LP ...
Страница 39: ...39 GI IM048En 1013 D INTERNAL WIRING DIAGRAM Figure 21 Wiring Diagram LP ...
Страница 40: ...40 GI IM048En 1013 Figure 22 LP 179 L LP ...
Страница 49: ...49 GI IM048En 1013 Figure 26 LP 179 J LP ...
Страница 50: ...50 GI IM048En 1013 Figure 27 LP 179 H LP ...
Страница 52: ...52 GI IM048En 1013 MAINTENANCE NOTES ...