Wired controller
GIA
-XK46
5
5
Wired Controller XK46
63
Error
Code
Content
Error
Code
Content
Error
Code
Content
Error
condenser
F6
Compressor 2 Discharge
Temperature Sensor
Error
J6
Compressor 6
Over-current Protection
bF
Malfunction of exit tube
temperature sensor of
condenser
F7
Compressor 3 Discharge
Temperature Sensor
Error
J7
4-way Valve Blow-by
Protection
bH
System Clock
Malfunction
F8
Compressor 4 Discharge
Temperature Sensor
Error
J8
System Pressure
Over-Ratio Protection
bJ
High and low pressure
sensors are connected
inversely
F9
Compressor 5 Discharge
Temperature Sensor
Error
J9
System Pressure
Under-Ratio Protection
bL
Compressor 2 Top
Temperature Sensor
Detachment Protection
FA
Compressor 6 Discharge
Temperature Sensor
Error
JA
Protection of Abnormal
Pressure
P0
Compressor Drive Board
Error
Fb
Compressor 2 Top
Temperature Sensor
Error
JC
Protection of Water
Flow Switch
P1
Compressor Drive Board
Malfunction
FC
Compressor 2 Current
Sensor Error
JE
Oil return pipe is
blocked
P2
Protection of
Compressor Drive Board
Power Supply
Fd
Mode Exchanger Outlet
Pipe Temperature Sensor
Error
JF
Oil return pipe is
leaking
P3
Protection of
Compressor Drive Board
Module Reset
FE
Compressor 4 Current
Sensor Error
JL
Protection of Low
High-pressure
H0 Error of Fan Drive Board
Wired Controller XK46
64
Error
Code
Content
Error
Code
Content
Error
Code
Content
FF
Compressor 5 Current
Sensor Error
b1
Outdoor Ambient
Temperature Sensor
Error
H1
Malfunction of Fan Drive
Board
FH
Compressor 1 Current
Sensor Error
b2
Defrosting
Temperature Sensor 1
Error
H2
Protection of Fan Drive
Board Power Supply
FJ
Compressor 6 Current
Sensor Error
b3
Defrosting
Temperature Sensor 2
Error
7.2 TABLE OF ERROR CODES FOR INDOOR UNIT
Error
Code
Content
Error
Code
Content
Error
Code
Content
L0
Indoor Unit Error
LF
Shunt Valve Setting
Error
d9
Jumper Cap Error
L1
Indoor Fan Protection
LH
Low Air Quanlity
Warning
dA
Indoor Unit
Hardware Address Error
L2
E-heater Protection
LJ
Wrong Setting of
Function DIP Switch
db
Special Code:
Field Debugging Code
L3
Water Full Protection
LP
Zero-crossing
malfunction of PG motor dC
Capacity DIP Switch
Setting Error.
L4
Wired Controller Power
Supply Error
LU
Inconsistent Branch of
Group-controlled Indoor
Units in Heat Recovery
System
dE Indoor Unit CO2 Sensor
Error
L5
Anti-Frosting Protection
d1
Indoor Unit PC-Board
Error
dH
Wired Controller
PC-Board Error
L7
No Master Indoor Unit
Error
d3
Ambient Temperature
Sensor Error
dL Outlet Air Temperature
Sensor Error
Содержание GIATSU GIA-XK46
Страница 35: ...Wired controller GIA XK46 35 Wired Controller XK46 40...
Страница 40: ...Wired controller GIA XK46 40 Wired Controller XK46 45 Fig 6 9 Setting of Quiet function in Celsius...
Страница 44: ...Wired controller GIA XK46 44 Wired Controller XK46 49 Fig 6 12 Turn on Air Function in Fahrenheit...
Страница 47: ...Wired controller GIA XK46 47 Wired Controller XK46 53 Fig 6 14 Save Setting for Cooling in Fahrenheit...