Wired controller
GIA
-XK46
19
Wired Controller XK46
Table 5.1 Parameters viewing list
Parameter
code
Parameter
name
Parameter
range
Viewing method
C00
Entrance of
adjustable
parameter
--
In “C00” status, Timer zone shows the current indoor
unit project number. When one wired controller is
controlling multiple indoor units, then only the
smallest project number will be displayed.
C01
View the
project
number of
indoor unit
and locate
the faulted
indoor unit
1-255;
Project
number of
online
indoor unit
Operation method:
Enter viewing, press MODE button in “C01” status to
enter the interface of viewing indoor unit project
number. Press “ ” or “
” button to select the
project number of indoor unit.
Display method:
Temperature zone: displays error codes of the
current indoor unit( The temperature zone will
display the error codes in turn with an interval of 3
seconds if there are several malfunctions in one
indoor unit.)
Timer zone: displays present indoor unit project
number /C5 malfunction of project number conflict
Note:
1) If master indoor unit exists in current indoor unit
network, “MASTER” icon will be bright under “C01”
interface. After entering the interface of viewing
project number, “MASTER” icon will be bright only
when the project number of master indoor unit is
selected.
2) System will not exit “C01” viewing automatically.
User has to exit this interface manually.
C03
View the
indoor unit
quantity of
the system
network
1-80
Timer zone: display indoor unit quantity of the
system
Wired Controller XK46
21
5.2 COMMISSIONING
5.2.1 Set Master Indoor Unit
Under Off status, long press MODE button for 5s to set the corresponding
indoor unit of wired controller as master indoor unit. “MASTER” icon will be light
after finishing setting.
Note:
①
There is a master indoor unit in a system, other slave indoor units can be set
as master unit, in which case, the original master unit will become a slave
unit.
②
In one system, only one set of master indoor unit is allowed. If system detects
that there are several master units, it will designate the unit with the smallest
project number as a master unit.
5.2.2 Parameter Enquiry
Unit parameters can be checked in unit On or Off status.
(1) Long press “FUNCTION” button for 5s to enter the interface of viewing unit
parameters. “C00” is displayed in temperature zone and “CHECK” icon is light;
(2) Press “ ” or “ ” button to select parameter code;
(3) Press “ENTER/CANCEL” button to return to last step until exits
viewing
parameters.
The parameter enquiry list is as following:
Содержание GIATSU GIA-XK46
Страница 35: ...Wired controller GIA XK46 35 Wired Controller XK46 40...
Страница 40: ...Wired controller GIA XK46 40 Wired Controller XK46 45 Fig 6 9 Setting of Quiet function in Celsius...
Страница 44: ...Wired controller GIA XK46 44 Wired Controller XK46 49 Fig 6 12 Turn on Air Function in Fahrenheit...
Страница 47: ...Wired controller GIA XK46 47 Wired Controller XK46 53 Fig 6 14 Save Setting for Cooling in Fahrenheit...