HD50
- 32 -
V1.5
Address
Type
Input Register description
1041 +
200 x (
N
-1)
B
Alarm for quantity associated to channel
N
if the channel is configured as
mapped 4…20 mA input:
0=OFF, 1=lower threshold alarm, 2=higher threshold alarm.
1042 +
200 x (
N
-1)
SW
Value of quantity associated to channel
N
if the channel is configured as
mapped potentiometric input.
1043 +
200 x (
N
-1)
B
Alarm for quantity associated to channel
N
if the channel is configured as
mapped potentiometric input:
0=OFF, 1=lower threshold alarm, 2=higher threshold alarm.
1044 +
200 x (
N
-1)
SW
Input value in
mV
of channel
N
. Only if channel
N
is configured as
0…10 V
input.
1045 +
200 x (
N
-1)
B
Alarm for channel
N
if the channel is configured as 0…10 V input:
0=OFF, 1=lower threshold alarm, 2=higher threshold alarm.
1046 +
200 x (
N
-1)
SW
Value of quantity associated to channel
N
if the channel is configured as
mapped 0…10 V input.
1047 +
200 x (
N
-1)
B
Alarm for quantity associated to channel
N
if the channel is configured as
mapped 0…10 V input:
0=OFF, 1=lower threshold alarm, 2=higher threshold alarm.
1050 +
200 x (
N
-1)
SW
Input value in
mV
of channel
N
(x100). Only if channel
N
is configured
as
-50…50 mV
input.
1051 +
200 x (
N
-1)
B
Alarm for channel
N
if the channel is configured as
-50…50 mV input:
0=OFF, 1=lower threshold alarm, 2=higher threshold alarm.
1052 +
200 x (
N
-1)
SW
Value of quantity associated to channel
N
if the channel is configured as
mapped -50…50 mV input.
1053 +
200 x (
N
-1)
B
Alarm for quantity associated to channel
N
if the channel is configured as
mapped -50…50 mV input:
0=OFF, 1=lower threshold alarm, 2=higher threshold alarm.
Measurement units and resolution
5000
W
Unit of measurement for
TEMPERATURE
with
NTC10K
sensor of channel
1
:
0=°C, 1=°F.
5004
W
D
EW POINT
measurement unit: 0=°C, 1=°F.
5012
W
W
ET BULB TEMPERATURE
measurement unit: 0=°C, 1=°F.
5016
W
Unit of measurement for
TEMPERATURE
with
NTC10K
sensor of channel
2
:
0=°C, 1=°F.
5021
SW
I
LLUMINANCE
resolution: -2=100, -1=10, 0=1
5024
W
A
TMOSPHERIC PRESSURE
measurement unit: see the table of indexes
5025
SW
A
TMOSPHERIC PRESSURE
resolution:
…, -2=100, -1=10, 0=1, 1=0.1, 2=0.01, …
5050
W
Unit of measurement for
TEMPERATURE
with
NTC10K
sensor of channel
3
:
0=°C, 1=°F.
5064
W
Unit of measurement for
TEMPERATURE
with
Pt100
sensor of HP3517E…
probe: 0=°C, 1=°F.
5084
W
D
IFFERENTIAL
PRESSURE
measurement unit: see the table of indexes
5085
SW
D
IFFERENTIAL
PRESSURE
resolution:
…, -2=100, -1=10, 0=1, 1=0.1, 2=0.01, …
6000 +
200 x (
N
-1)
W
Unit of measurement for
TEMPERATURE
with
2-wire Pt100
sensor of
channel
N
: 0=°C, 1=°F.
6002 +
200 x (
N
-1)
W
Unit of measurement for
TEMPERATURE
with
3-wire Pt100
sensor of
channel
N
: 0=°C, 1=°F.
6004 +
200 x (
N
-1)
W
Unit of measurement for
TEMPERATURE
with
4-wire Pt100
sensor of
channel
N
: 0=°C, 1=°F.