5.1 Mounting kit without window
for DV DIASTAR DN 15–DN 150
5.1.3 The needle (¢2) is centered in the
adapter (¢–5) with the corresponding
parts (remove indicator disk). (For DN
100–150 also place the needle
protector on the needle and then
insert in adapter).
5.1.4 Place o-ring (6) on adapter (7) and screw
onto DV DIASTAR
(Check the distance
Yu, see below)
.
5.1.5 Insert DSR positioner (8) in adapter (7)
and fasten with threaded studs (9).
5.1.6 Remove the lower protective plug (FC).
Connect rapid connector (10) on
actuator and positioner.
5.1.7 Connect the hose (11) between DV
DIASTAR and DSR positioner
(connection A).
5.1.8 Connect air supply to connector P.
–
Direct version
Diastar &
Mechanical check
Positioner
area Yu
closed
DN 15 Gr. 2
46.8–47.3
DN 20 Gr. 2
50.4–51.2
DN 25 Gr. 2
50.8–52.1
DN 25 Gr. 3
54.3–56.3
DN 32 Gr. 3
55.5–57.2
DN 32 Gr. 4
47.5–48.6
DN 40 Gr. 4
52.8–54.0
DN 40 Gr. 5
52.2–55.1
DN 50 Gr. 4
56.8–57.4
DN 50 Gr. 5
55.8–58.1
DN 65
71.4–73.4
DN 80
75.8–76.9
DN 100
75.6–77.4
DN 150
77.0–77.4
All dimensions in mm
Yu
Connect
or
A
Yu = distance required for correct instal-
lation of adapters
Connect
or
P