GEZE SecuLogic RWS TZ 300 Скачать руководство пользователя страница 4

SECULOGIC TZ300

4

About this document

Abbreviations

1.4 

 

Abbreviation

Meaning

AKRR

Feedback contact interlocked (actuated by the anchor) 

BLE220

Flashlight

BMA

Fire detection system

FS

Latch lock

FTÖ

Emergency exit door opener

GCDU100

Single-door unit

GCDU200

Door unit

GCFP401

Fingerprint

GCRR200

RFiD card reader 

GCVR200

RFiD card reader

GLT

Building services management

GMA

Hazard alert system

IQ Lock C

Self-locking contact lock

IQ Lock EL

Self-locking motor lock

IQ Lock EM

Self-locking lever lock

IQ Lock M

Self-locking mechanical panic lock

KZF

Short-term release

MA500

Holding magnet

NC

Floating NC (normally closed) contact

NO

Floating NO (normally open) contact

NOT320

Emergency button

PSU

Power supply unit

OKFF

Upper edge of finished floor

RR

“Door closed” feedback contact (actuated through sliders on the latch)

RWA

Smoke and heat extraction system

SCT221

Key-operated pushbutton, single-pole pushbutton (NO), extendable to single-pole reversing (two NO)

SCT222

Key switch with LED indicator, single-pole reversing (two NO)

SCT320

Key switch, single-pole reversing (two NO)

SHB220

Alarm bell with flashlight

SLE220

Signal lamp

SLH220

Alarm bell

TZ300S

Door control unit with key switch (connection through ribbon cable)

TZ300S

Door control unit with key switch and built-in PSU

ZSU

Timer

Содержание SecuLogic RWS TZ 300

Страница 1: ...1 GEZE SECULOGIC TZ300 Emergency Exit System Door Control Unit EN Installation and Commissioning Instructions with Wiring Diagram...

Страница 2: ...2 4 1 Preconditions 12 4 2 Settings 12 4 3 Description of basic functions 12 4 4 Fire detection system BMA hazard alert system GMA smoke and heat extraction system RWA 13 5 Operation 14 5 1 Controllin...

Страница 3: ...al ling interface to the building services management system Built in buzzers and LEDs provide visual and audible indication when an alarm has been triggered Related documents 1 2 All components are s...

Страница 4: ...lock KZF Short term release MA500 Holding magnet NC Floating NC normally closed contact NO Floating NO normally open contact NOT320 Emergency button PSU Power supply unit OKFF Upper edge of finished...

Страница 5: ...ion of the emergency exit system for visible damage and X X faults by the owner Any identified damage or faults must be rectified immediately by a GEZE service technici an or a GEZE authorized service...

Страница 6: ...ds VDE 0100 und VDE 0815 for laying cables Tamper proof cable routing according to VDE 0833 surface mounted cables in steel conduit For flush mounted cabling flush mounted sockets depth 62 5 mm at a m...

Страница 7: ...mains cable and ribbon cable in the flush mounted sockets X X Connect cable to terminal blocks according to wiring diagram X X 850 1200 60 71 71 6 2 5 Connect and fit the PSU X X Connect the key switc...

Страница 8: ...LOGIC TZ300 8 Installation and assembly Fit the terminal blocks to the back of the door control unit X X C C D D Fit the door control unit X X Fit the green adhesive frame X X Test the unit s function...

Страница 9: ...SECULOGIC TZ300 9 Installation and assembly Fitting the surface mounted door control unit 3 3 1 2 Door control unit TZ300SN 1 Terminal blocks 2 Open the housing X X...

Страница 10: ...e to terminal blocks according to wiring diagram X X Fit the terminal blocks to the back of the door control unit X X Secure loose cables with cable ties X X Hook in housing and secure with screws X X...

Страница 11: ...Release cap screw and remove the lock cylinder X X Fitting a safety cylinder length 40 10 3 5 If using a safety cylinder with 50 mm 40 10 use the spacers between key switch and housing Fit the spacer...

Страница 12: ...is then unlocked To lock it turn the key switch to the right again Settings 4 2 No settings can be made or changed on the door control unit All values such as short term release cancelling pre alarm e...

Страница 13: ...A hazard alert system GMA smoke and heat 4 4 extraction system RWA Alarm triggers 4 4 1 If the BMA GMA or RWA signal of a door control unit is applied it is unlocked and a local alarm is triggered aud...

Страница 14: ...rol unit with emergency button 3 Locked LED 1 Door state LED 2 Alarm LED 3 No Indicator Colour Meaning 1 Red Locked Green Unlocked Green flashing every second Short term release 2 Red Door closed Gree...

Страница 15: ...an be opened Turn the key to the left and hold it for about one second X X 1 2 3 LED 1 lights up green The door is unlocked Locking the door When the system is unlocked the locking elements are enable...

Страница 16: ...tive the short term release period starts again is retriggered Precondition The door is locked Turn the key to the right X X 2 3 1 LED 1 flashes green The door remains unlocked for the set period of 2...

Страница 17: ...econdition The alarm cause has been eliminated To acknowledge the alarm and lock the door Turn the key to the right X X To acknowledge the alarm and unlock the door Turn the key to the left X X The do...

Страница 18: ...arm Alarm LED Alarm bell Pre alarm Yellow flashing light 1 s on 1 s off Acoustic signal 2 beeps Door alarm Yellow continuous light Acoustic signal 2 seconds continuous Tamper alarm Yellow continuous l...

Страница 19: ...X and 10 Locking element connected with reversed polarity Emergency button LED goes on and off Other LEDs remain off With PSUs NET220 und NT19 2 24 With larger PSUs the fuse blows Immediately isolate...

Страница 20: ...90 Alarm bell with flashlight 110 Holding magnet MA500 250 Alarm bell SLE220 16 Emergency exit door opener FT 331 160 Key switch with LED SCT222 30 Emergency exit door opener FT 332 105 Relay card RP2...

Страница 21: ...ernal devices with standard PSU of the TZ300 UP NET220 max 350 mA AP NT19 2 24 max 650 mA with external PSU max 800 mA use only GEZE approved PSUs Terminal assignment Max cable cross section for screw...

Страница 22: ...ernally 3 TZ300SN UP Protection class II PE protective earth conductor is not connected TZ300SN AP Protection class I with PE conductor testing according to VDE0100 4 In delivery state the 2K resistor...

Страница 23: ...SECULOGIC TZ300 23 Wiring diagram Door control unit TZ300S TZ300SN 6 4 3 blue For notes about the wiring diagram see section 6 4 2...

Страница 24: ...blue X100 red 24 V DC Lock SCT KZF acknowledge Unlock SCT acknowledge Tamper GEZE SCT320 Key switch TST300 Connection to TST300 X103 Plug for GEZE key switch X102 or X103 Ribbon cable X100 red termin...

Страница 25: ...SECULOGIC TZ300 25 Wiring diagram Emergency unlocking through BMA GMA or RWA 6 4 5 For notes about the wiring diagram see section 6 4 2...

Страница 26: ...l cables in series Programming interface red blue Holding magnet MA500 single leaf doors 6 5 1 TST300 X101 orange terminal strip Door contact Locking Locking Door locked 24 V DC Door closed 24 V DC Ho...

Страница 27: ...minal strip 5 14 6 15 2 2 8 7 6 FT 331U 5 4 3 NO COM NC NO COM NC AKRR RR 2 8 7 6 FT 331U 5 4 3 NO COM NC NO COM NC AKRR RR A B A B 1 1 Locking Locking Door locked 24 V DC Door closed Caution Sever re...

Страница 28: ...ocking Door locked 24 V DC Door closed Emergency door opener TYP331 DIN left two leaf doors 6 5 7 X101 orange terminal strip 5 14 6 15 2 2 4 5 6 RD GN BU NO COM NC NO COM NC AKRR RR NO COM NC NO COM N...

Страница 29: ...WW No 094012 UP GIRA E2 pure white Closed on right Closed on left COM Key switch SCT221 SCT to short term release 6 6 3 Brief unlocking input 24 V DC orange terminal strip No 094170 UP Jung LS990 stai...

Страница 30: ...ledge Unlock SCT acknowledge Tamper key switch No 132278 UP GIRA E2 anthracite No 130370 UP GIRA E2 pure white No 131984 UP Jung AS500 WW Key switch SCT220 for external control 6 6 5 unlocking locking...

Страница 31: ...ked 24 V DC Door closed Brief unlocking input 24 V DC Emergencyunlockinginput 24 V DC orange terminal strip Caution Order of terminals not as on terminal strip blue terminal strip 24 V DC Alarm output...

Страница 32: ...cal code lock Toplock CTI CTI B 6 7 1 X102 blue or X100 red X101 orange terminal strip Brief unlocking input Numerical codelock Toplock CTS V CTS BV 6 7 2 Number codelock Toplock CTS V CTS BV Brief un...

Страница 33: ...V DC orange terminal strip Optionally the GCDU100 can be supplied with power through the TZ300 Observe total power consumption Supply GND 24 V DC supply X100 red terminal strip Timer 6 8 Brief unlock...

Страница 34: ...key switch Access control Button etc Floating NO contact required Lock connection cable red wire Magnet black wire Magnet red blue wire COM cylinder contact grey pink wire NO cylinder contact Caution...

Страница 35: ...he outer lever handle of the IQ Lock EM is disengaged When the TZ300 is temporarily or permanently unlocked the outer lever handle is engaged Option 1 When the cylinder contact of IQ Lock is connected...

Страница 36: ...ergency button illumination working Emergency button function OK Tamper switches working correctly Unlocking through key switch is working correctly Locking through key switch is working correctly Fee...

Страница 37: ...0 seconds If the door is closed while a pre alarm is active the door is locked automatically and the pre alarm is reset Door alarm If the pre alarm time is exceeded the door alarm is triggered This mu...

Страница 38: ...voltage 24 V DC 10 Power consumption 100 mA at 24 V DC w o peripherals Total power consumption 1 A at 24 V DC depending on PSU used Protection class II according to EN 60950 in built in state Mountin...

Страница 39: ...w o peripherals Total power consumption Versions with PSU 800 mA Versions without PSU Max 1A depending on PSU used Protection class Versions with PSU I according to EN 60950 Versions without PSU II a...

Страница 40: ...0 to 50 C Package content Emergency exit sign module green border Key switch SCT320UP 7 3 4 Technical specifications Device name Key switch SCT320UP Versions White Anthracite Pure white Function Key s...

Страница 41: ...SECULOGIC TZ300 41...

Страница 42: ...SECULOGIC TZ300 42...

Страница 43: ...SECULOGIC TZ300 43...

Страница 44: ...est H 1115 Tel 36 1 481 4670 Fax 36 1 481 4671 E Mail office hungary geze com Iberia GEZE Iberia S R L Pol Ind El Pla C Comerc 2 22 Nave 12 08980 Sant Feliu de Llobregat Barcelona Tel 34 0 9 02194036...

Отзывы: