SECULOGIC TZ300
24
Wiring diagram
TZ300SN, TZ300S: Door monitor without locking element
6.4.4
For use, for example, as door monitor
Function:
The door can be opened at any time through the panic handle.
Opening the door without authorization triggers the door alarm, which, in turn, triggers a visual and acoustic alarm
through the built-in signal generators. The door alarm remains active until the door is closed again and the alarm is
reset with the built-in key switch or through the Short-term release input.
Authorized access is possible with short-term release function or by permanently unlocking the door.
X102 (blue)
X100
(red)
24 V DC
Lock SCT, KZF, acknowledge
Unlock SCT, acknowledge
Tamper
GEZE SCT320
Key switch
TST300
Connection to
TST300 X103
Plug for GEZE
key switch
X102 or X103
Ribbon cable
X100 (red terminal strip)
Supply GND
24 V DC supply
Power supply unit
Screw terminal
Relay card RP220
Nr. 102355
Door contact
Temporary unlocking through:
- External key switch
- Access control
- Cylinder contact
- Button, etc.
Floating NO contact required
Signal lamp
Alarm bell
Optionally for additional acoustic and/or visual
alarm signalling.
Observe max. total power consumption of TZ300SN.
L
Locking -
Door locked
24 V DC
Door closed
Brief unlocking input
24 V DC
Emergencyunlockinginput
24 V DC
X101 (orange terminal strip)
Caution: Order of terminals not as
on terminal strip
Alarm
output
max. 1 A,
24 V DC
X102 (blue terminal strip)