GEZE IO 420
GEZE IO 420
11
10
71.ZSUMASTER4_SUNDAY(0/1)
72.ZSUMASTER4_MONDAY(0/1)
73.ZSUMASTER4_TUESDAY(0/1)
74.ZSUMASTER4_WEDNESDAY(0/1)
75.ZSUMASTER4_THURSDAY(0/1)
76.ZSUMASTER4_FRIDAY(0/1)
77.ZSUMASTER4_SATURDAY(0/1)
=
=
=
=
=
=
=
0;
0;
0;
0;
0;
0;
0;
Day configuration “ZSU master group 4”
0: as “ZSU master group 4” inactive on this day of the week
1: as “ZSU master group 4” active on this day of the week
78.ZSUMASTER4_START_HH(0~23)
79.ZSUMASTER4_START_MM(0~59)
=
=
0;
0;
Start time “ZSU master group 4”
Specification of “hours” 0-23; specification of “minutes” 0-59
80.ZSUMASTER4_END_HH(0~23)
81.ZSUMASTER4_END_MM(0~59)
=
=
0;
0;
End time “ZSU master group 4”
Specification of “hours” 0-23; specification of “minutes” 0-59
82.ZSUMASTER5_ACTIVITY(0/1)
=
0;
0: as “ZSU master group 5” not active.
1: as “ZSU master group 5” active.
83.ZSUMASTER5_SUNDAY(0/1)
84.ZSUMASTER5_MONDAY(0/1)
85.ZSUMASTER5_TUESDAY(0/1)
86.ZSUMASTER5_WEDNESDAY(0/1)
87.ZSUMASTER5_THURSDAY(0/1)
88.ZSUMASTER5_FRIDAY(0/1)
89.ZSUMASTER5_SATURDAY(0/1)
=
=
=
=
=
=
=
0;
0;
0;
0;
0;
0;
0;
Day configuration “ZSU master group 5”
0: as “ZSU master group 5” inactive on this day of the week
1: as “ZSU master group 5” active on this day of the week
90.ZSUMASTER5_START_HH(0~23)
91.ZSUMASTER5_START_MM(0~59)
=
=
0;
0;
Start time “ZSU master group 5”
Specification of “hours” 0-23; specification of “minutes” 0-59
92.ZSUMASTER5_END_HH(0~23)
93.ZSUMASTER5_END_MM(0~59)
=
=
0;
0;
End time “ZSU master group 5”
Specification of “hours” 0-23; specification of “minutes” 0-59
94.DOOR1_SLAVEZSU_GR1(0/1)
95.DOOR1_SLAVEZSU_GR2(0/1)
96.DOOR1_SLAVEZSU_GR3(0/1)
97.DOOR1_SLAVEZSU_GR4(0/1)
98.DOOR1_SLAVEZSU_GR5(0/1)
=
=
=
=
=
0;
0;
0;
0;
0;
Slave assignment of door #1 to “ZSU master group” 1 to 5
0: Door #1 is not part of this ZSU group
1: Door #1 is part of this ZSU group
99.DOOR1_SLAVEZSU_ABORT(0/1)
=
0;
0: Time switch function for door #1 not interruptible
1: Time switch function for door #1 interruptible
100.DOOR2_SLAVEZSU_GR1(0/1)
101.DOOR2_SLAVEZSU_GR2(0/1)
102.DOOR2_SLAVEZSU_GR3(0/1)
103.DOOR2_SLAVEZSU_GR4(0/1)
104.DOOR2_SLAVEZSU_GR5(0/1)
=
=
=
=
=
0;
0;
0;
0;
0;
Slave assignment of door #2 to “ZSU master group” 1 to 5
0: Door #1 is not part of this ZSU group
1: Door #1 is part of this ZSU group
105.DOOR2_SLAVEZSU_ABORT(0/1) =
0;
0: Time switch function for door #2 not interruptible
1: Time switch function for door #2 interruptible
106.DOOR3_SLAVEZSU_GR1(0/1)
107.DOOR3_SLAVEZSU_GR2(0/1)
108.DOOR3_SLAVEZSU_GR3(0/1)
109.DOOR3_SLAVEZSU_GR4(0/1)
110.DOOR3_SLAVEZSU_GR5(0/1)
=
=
=
=
=
0;
0;
0;
0;
0;
Slave assignment of door #3 to “ZSU master group” 1 to 5
0: Door #3 is not part of this ZSU group
1: Door #3 is part of this ZSU group
111.DOOR3_SLAVEZSU_ABORT(0/1) =
0;
0: Time switch function for door #3 not interruptible
1: Time switch function for door #3 interruptible
112.DOOR4_SLAVEZSU_GR1(0/1)
113.DOOR4_SLAVEZSU_GR2(0/1)
114.DOOR4_SLAVEZSU_GR3(0/1)
115.DOOR4_SLAVEZSU_GR4(0/1)
116.DOOR4_SLAVEZSU_GR5(0/1)
=
=
=
=
=
0;
0;
0;
0;
0;
Slave assignment of door #4 to “ZSU master group” 1 to 5
0: Door #4 is not part of this ZSU group
1: Door #4 is part of this ZSU group
117.DOOR4_SLAVEZSU_ABORT(0/1) =
0;
0: Time switch function for door #4 not interruptible
1: Time switch function for door #4 interruptible
118.TYPE OF CP(0~3)
=
0;
0: no CP
1: one CP
2: two CPs
3: Pin “+24V” and “DET” of the connection “CP” are
short-circuited together.
“CP” are short-circuited together.
END OF FILE---------------------------
5
Module description
The IO 420 offers 10 module types. The respective inputs/outputs are used in different ways depending on the
module type.
5.1 Module type “watchdog”
The “watchdog” module type can be used for monitoring a door. When the monitoring function is armed,
the door may only be opened by release. In all other cases, an alarm message is sent after the alarm suppression
and alarm delay times have expired.
When the monitoring function is not armed, the door can be opened without release.
Connections
Assignment/function description
Menu
Input
1
à
rising flank
- monitoring is disarmed
à
falling flank -
monitoring is armed
Duration for
short-term
release
2
Release with short-term release function; only with rising flank
3
Bolt feedback
4
Door contact
Output
1
Monitoring state; enabled with armed monitoring
2
Electric strike fail safe
3
Alarm suppressed: 1 sec cycle
Alarm delayed: on
Alarm enabled: off
4
Alarm suppressed: off
Alarm delayed: off
Alarm enabled: Permanently on
Tab. 1: Pin assignment for “watchdog” module type
Functional description of the inputs and outputs
current state – current state
State changes to
State changes with
Monitoring disarmed
Alarm active
Sabotage
Monitoring armed
à
falling flank at input 1
à
CAN command “watchdog enable”
à
BACnet command “watchdog enable”
Monitoring armed
Alarm active
Sabotage
Monitoring disarmed
à
rising flank at input 1
à
CAN command “watchdog disable”
à
BACnet command “watchdog disable”
Alarm suppressed
If the door is locked but open
Alarm suppressed
(output 1 enabled and output 3 flashing
every few seconds)
Alarm active
Sabotage
Monitoring disarmed
à
rising flank at input 1
à
CAN command “watchdog disable”
à
BACnet command “watchdog disable”
Monito
ring armed
If the alarm activation has been cancelled
and the alarm acknowledged.
Alarm delayed
If the alarm suppression time has expired.
Alarm delayed
(output 1 and 3 enabled.)
Alarm active
à
Sabotage
à
If the alarm delay time has expired.
Monitoring armed
(if the alarm activation has been cancelled
and a command sent either via input 2,
CAN or BACnet as acknowledgement to the
IO 420.)
à
Short-term release through input 2
à
CAN command “watchdog enable”,
“watchdog disable” or “KZF”
à
BACnet command “KZF”
Alarm enabled
(output 1 and 4 enabled.)
Monitoring armed
(if the alarm activation has been cancelled
and a command sent either via input 2,
CAN or BACnet as acknowledgement to the
IO 420.)
à
Short-term release through input 2
à
CAN command “watchdog enable”,
“watchdog disable” or “KZF”
à
BACnet command “KZF”