71.ZSUMASTER4_SUNDAY(0/1)    

72.ZSUMASTER4_MONDAY(0/1)    

73.ZSUMASTER4_TUESDAY(0/1)   

74.ZSUMASTER4_WEDNESDAY(0/1) 

75.ZSUMASTER4_THURSDAY(0/1)  

76.ZSUMASTER4_FRIDAY(0/1)    

77.ZSUMASTER4_SATURDAY(0/1)  

=

=

=

=

=

=

=

0;

0;

0;

0;

0;

0;

0;

Day configuration “ZSU master group 4”

0: as “ZSU master group 4” inactive on this day of the week

1: as “ZSU master group 4” active on this day of the week

78.ZSUMASTER4_START_HH(0~23) 

79.ZSUMASTER4_START_MM(0~59) 

=

=

0;

0;

Start time “ZSU master group 4”

Specification of “hours” 0-23; specification of “minutes” 0-59

80.ZSUMASTER4_END_HH(0~23)   

81.ZSUMASTER4_END_MM(0~59)   

=

=

0;

0;

End time “ZSU master group 4”

Specification of “hours” 0-23; specification of “minutes” 0-59

82.ZSUMASTER5_ACTIVITY(0/1)  

=

0;

0: as “ZSU master group 5” not active.

1: as “ZSU master group 5” active.

83.ZSUMASTER5_SUNDAY(0/1)    

84.ZSUMASTER5_MONDAY(0/1)    

85.ZSUMASTER5_TUESDAY(0/1)   

86.ZSUMASTER5_WEDNESDAY(0/1) 

87.ZSUMASTER5_THURSDAY(0/1)  

88.ZSUMASTER5_FRIDAY(0/1)    

89.ZSUMASTER5_SATURDAY(0/1)  

=

=

=

=

=

=

=

0;

0;

0;

0;

0;

0;

0;

Day configuration “ZSU master group 5”

0: as “ZSU master group 5” inactive on this day of the week

1: as “ZSU master group 5” active on this day of the week

90.ZSUMASTER5_START_HH(0~23) 

91.ZSUMASTER5_START_MM(0~59) 

=

=

0;

0;

Start time “ZSU master group 5”

Specification of “hours” 0-23; specification of “minutes” 0-59

92.ZSUMASTER5_END_HH(0~23)   

93.ZSUMASTER5_END_MM(0~59)   

=

=

0;

0;

End time “ZSU master group 5”

Specification of “hours” 0-23; specification of “minutes” 0-59

94.DOOR1_SLAVEZSU_GR1(0/1)

   

95.DOOR1_SLAVEZSU_GR2(0/1)   

96.DOOR1_SLAVEZSU_GR3(0/1)   

97.DOOR1_SLAVEZSU_GR4(0/1)   

98.DOOR1_SLAVEZSU_GR5(0/1)   

=

=

=

=

=

0;
0;

0;

0;

0;

Slave assignment of door #1 to “ZSU master group” 1 to 5

0: Door #1 is not part of this ZSU group

1: Door #1 is part of this ZSU group 

99.DOOR1_SLAVEZSU_ABORT(0/1)

=

0;

0: Time switch function for door #1 not interruptible

1: Time switch function for door #1 interruptible

100.DOOR2_SLAVEZSU_GR1(0/1)  

101.DOOR2_SLAVEZSU_GR2(0/1)  

102.DOOR2_SLAVEZSU_GR3(0/1)  

103.DOOR2_SLAVEZSU_GR4(0/1)  

104.DOOR2_SLAVEZSU_GR5(0/1)  

=

=

=

=

=

0;

0;

0;

0;

0;

Slave assignment of door #2 to “ZSU master group” 1 to 5

0: Door #1 is not part of this ZSU group

1: Door #1 is part of this ZSU group 

105.DOOR2_SLAVEZSU_ABORT(0/1) =

0;

0: Time switch function for door #2 not interruptible

1: Time switch function for door #2 interruptible

106.DOOR3_SLAVEZSU_GR1(0/1)  
107.DOOR3_SLAVEZSU_GR2(0/1)

  

108.DOOR3_SLAVEZSU_GR3(0/1)  

109.DOOR3_SLAVEZSU_GR4(0/1)  

110.DOOR3_SLAVEZSU_GR5(0/1)  

=

=

=

=

=

0;

0;

0;

0;

0;

Slave assignment of door #3 to “ZSU master group” 1 to 5

0: Door #3 is not part of this ZSU group

1: Door #3 is part of this ZSU group 

111.DOOR3_SLAVEZSU_ABORT(0/1) =

0;

0: Time switch function for door #3 not interruptible

1: Time switch function for door #3 interruptible

112.DOOR4_SLAVEZSU_GR1(0/1)  

113.DOOR4_SLAVEZSU_GR2(0/1)  

114.DOOR4_SLAVEZSU_GR3(0/1)  

115.DOOR4_SLAVEZSU_GR4(0/1)  

116.DOOR4_SLAVEZSU_GR5(0/1)  

=

=

=

=

=

0;

0;

0;

0;

0;

Slave assignment of door #4 to “ZSU master group” 1 to 5

0: Door #4 is not part of this ZSU group

1: Door #4 is part of this ZSU group 

117.DOOR4_SLAVEZSU_ABORT(0/1) =

0;

0: Time switch function for door #4 not interruptible

1: Time switch function for door #4 interruptible

118.TYPE OF CP(0~3)          

=

0;

0: no CP

 

1: one CP

2: two CPs

3: Pin “+24V” and “DET” of the connection “CP” are  

short-circuited together. 

“CP” are short-circuited together.

END OF FILE---------------------------

Module description

The IO 420 offers 10 module types. The respective inputs/outputs are used in different ways depending on the 

module type.

5.1   Module  type  “watchdog”

The “watchdog” module type can be used for monitoring a door. When the monitoring function is armed,  

the door may only be opened by release. In all other cases, an alarm message is sent after the alarm suppression 

and alarm delay times have expired.  

When the monitoring function is not armed, the door can be opened without release.

Connections

Assignment/function description

Menu

Input

1

 

à

rising flank

 - monitoring is disarmed

 

à

falling flank - 

monitoring is armed

Duration for 

short-term 

release

2

Release with short-term release function; only with rising flank

3

Bolt feedback

4

Door contact

Output

1

Monitoring state; enabled with armed monitoring

2

Electric strike fail safe

3

Alarm suppressed: 1 sec cycle

Alarm delayed: on

Alarm enabled: off

4

Alarm suppressed: off

Alarm delayed: off

Alarm enabled: Permanently on

Tab. 1: Pin assignment for “watchdog” module type

Functional description of the inputs and outputs

current state – current state

State changes to

State changes with

Monitoring disarmed

Alarm active

Sabotage

Monitoring armed

 

à

falling flank at input 1

 

à

CAN command “watchdog enable”

 

à

BACnet command “watchdog enable”

Monitoring armed

Alarm active

Sabotage

Monitoring disarmed

 

à

rising flank at input 1

 

à

CAN command “watchdog disable”

 

à

BACnet command “watchdog disable”

Alarm suppressed

If the door is locked but open

Alarm suppressed

(output 1 enabled and output 3 flashing 

every few seconds)

Alarm active

Sabotage

Monitoring disarmed

 

à

rising flank at input 1

 

à

CAN command “watchdog disable”

 

à

BACnet command “watchdog disable”

Monito

ring armed

If the alarm activation has been cancelled 

and the alarm acknowledged.

Alarm delayed

If the alarm suppression time has expired.

Alarm delayed

(output 1 and 3 enabled.)

Alarm active

 

à

Sabotage

 

à

If the alarm delay time has expired.

Monitoring armed 

(if the alarm activation has been cancelled 

and a command sent either via input 2, 

CAN or BACnet as acknowledgement to the 

IO 420.)

 

à

Short-term release through input 2

 

à

CAN command “watchdog enable”, 

“watchdog disable” or “KZF”

 

à

BACnet command “KZF”

Alarm enabled 

(output 1 and 4 enabled.)

Monitoring armed 

(if the alarm activation has been cancelled 

and a command sent either via input 2, 

CAN or BACnet as acknowledgement to the 

IO 420.)

 

à

Short-term release through input 2

 

à

CAN command “watchdog enable”, 

“watchdog disable” or “KZF”

 

à

BACnet command “KZF”

Содержание IO 420

Страница 1: ...IO 420 164898 04 EN User manual IO 420 161864 03 DE Benutzerhandbuch...

Страница 2: ...iese Warnhinweise immer X Befolgen Sie alle Ma nahmen die mit dem Warnsymbol und Warnwort gekennzeichnet sind Warnsymbol Warnwort Bedeutung VORSICHT Informationen zur Vermeidung von Sachsch den zum Ve...

Страница 3: ...0 erf llt folgende Normen DIN EN 61000 6 2 2005 entsprechend VDE 0839 Teil 6 2 M rz 2006 DIN EN 61000 6 6 2007 A1 2011 entsprechend VDE 0839 Teil 6 3 September 2011 3 Produkt bersicht Montagehinweise...

Страница 4: ...microSD Card gelesen oder geschrieben wird LED 2 gelb LED leuchtet wenn CP Kondensatorplatine angeschlossen ist LED 3 rot LED blinkt bei St rung LED 4 gr n LED blinkt im normalen Betrieb LED 5 gr n LE...

Страница 5: ...SDAY 0 1 40 ZSUMASTER1_FRIDAY 0 1 41 ZSUMASTER1_SATURDAY 0 1 0 0 0 0 0 0 0 Day configuration ZSU master group 1 0 as ZSU master group 1 inactive on this day of the week 1 as ZSU master group 1 active...

Страница 6: ..._GR4 0 1 116 DOOR4_SLAVEZSU_GR5 0 1 0 0 0 0 0 Slave assignment of door 4 to ZSU master group 1 to 5 0 Door 4 is not part of this ZSU group 1 Door 4 is part of this ZSU group 117 DOOR4_SLAVEZSU_ABORT 0...

Страница 7: ...longer enabled Time switch interruption If time switch interruptible is enabled in the IO 420 configuration the time switch state can be interrupted using the lock command The state then changes to l...

Страница 8: ...atic 4 sec is enabled output 3 is switched off again after 4 seconds night falling flank input 1 CAN command night BACnet command night shop closed CAN command close shop BACnet command close shop per...

Страница 9: ...Die Verwendung von Sonderzeichen ist nicht erlaubt ausgenommen Leerzeichen Unterstrich Bindestrich Punkt und Komma 4 Parametrierung GEZE IO 420 Die erste Parametrierung des IO 420 sollte grunds tzlich...

Страница 10: ...rminal box The inputs and outputs of the IO 420 can be used as an IO extension for the TZ 320 KL 220 has 4 inputs and 6 outputs Since the IO 420 has 4 inputs and 4 outputs the configuration for the fi...

Страница 11: ...e IO 420 functions as gateway as in module type DCU 1 2 and 8 Therefore drives require DCU light so that the lifetime report is forwarded to IO 420 via Can Active leaves and passive leaves can also be...

Страница 12: ...sind folgende Punkte zu beachten Der Parametername einschlie lich dem Zeichen darf nicht ge ndert werden Das fungiert hier als Trennzeichen zwischen Titelteil und Wert Der Parameter Wert darf nur Zah...

Страница 13: ...19 3 1 4 N Y 5 door1_command 1 19 4 1 1 3 Y Y 6 door2_state 1 19 5 1 4 N Y 5 door2_command 1 19 6 1 1 3 Y Y 6 door3_state 1 19 7 1 4 N Y 5 door3_command 1 19 8 1 1 3 Y Y 6 door4_state 1 19 9 1 4 N Y...

Страница 14: ...d 1 19 4 1 1 3 Y Y 66 6 1 9 module type window Mandatory Optional Keyname Objectname device obj Inst object type object inst present value default min present value max present value command able supp...

Страница 15: ...N 4 door_state_DCU_SF 3 4 N N 4 Device_IO420 8 1 N N notification_class_obj 15 50 N N module_type 19 1 1 13 N N 1 Alarm_TZ 19 2 1 15 N N 6 50 operating_mode_DCU 19 3 1 14 N N 84 mode_command 19 4 1 1...

Страница 16: ...alarm de layed alarm active 61 automatic night shop close permanently open 62 night day release short time release 63 no command unlock lock short time release 66 enable watchdog disable watchdog shor...

Страница 17: ...unlocked 230V failure 54_DPS comm err unknown error unknown error 57_Smoke alarm SF unknown error unknown error 60_Err in control unit GF 61_Battery flat no error 94 78_Excess temperature SF 79_Motor...

Страница 18: ...4 sec Window Universal Conf relay 1 Conf ZSU slave 1 ZSU slave size 1 ZSU slave size 2 ZSU slave size 3 ZSU slave size 4 ZSU slave size 5 Yes no Yes no Yes no Yes no Yes no No No No No No Conf ZSU int...

Страница 19: ...on sheet The object descriptions cannot be backed up and must be entered again manually Firmware update Firmware updates are provided by GEZE in electronic form Copy the hex file to the directory Flas...

Страница 20: ...2Pfs bat 11 FlashData IO420 IO420_V1 RICHTIG Flasher STM32 ProgSTM32Pfs bat 3 FlashData IO420 IO420_V1 GEZE IO 420 35 Abb 7 COM Port Einstellung im Ger te Manager X Datei IO420_Flasher bat erneut ausf...

Страница 21: ...nce fr geze com www geze fr Hungary GEZE Hungary Kft E Mail office hungary geze com www geze hu Iberia GEZE Iberia S R L E Mail info es geze com www geze es India GEZE India Private Ltd E Mail office...

Отзывы: