GEZE hold-open system FA GC 150

27

Technical data

4.11  Manual trigger switch UTA

Type

UTA, AS500

Manual trigger switch

ID 116266

Surface-mounted box

ID 120503

Spare resistor 43 kΩ

ID 157093

Type of switching

Changer

Switching voltage

Maximum 250 V

Switching current

maximum 10 A

Terminating resistor

43 kΩ

Close door

Fig. 4.11.1

43k

 

Fig. 4.11.2

4.12  Wireless input module GC 175

Wireless input module GC 175

comprising:

ID 163068

 

ú

Wireless input module GC 175

 

ú

Main battery and slave batt

ery, resistor 2.2 kΩ

Battery set (VPE 10)

Spare resistor 2.2 kΩ

Main battery

Slave battery

Colour

ID 183282

ID 163229

Type CR 123A (3 V DC)

Type CR 2032A (3 V DC) 

Matt black

Dimensions (Ø × H)

52 mm × 32 mm

Functional principle

 

ú

signals the state of an external potential-free contact  

(normally open contact) to the GC 171 wireless module

 

ú

monitors the line to the contact for breaks

Line length

130 mm

Line monitoring

Termination resistor 2.2 kΩ at the end of the line

Installation position

Installation in flush-mounted or cavity box

Installation in such a way that removing the wireless module and 

manual trigger switch is only possible after these two assemblies 

have been disconnected from one another (e.g. installation of the 

two assemblies in two different flush-mounted boxes)

Service life main battery

5 years

Signal transfer period

60 s

Antenna

integrated

Frequency range

868.15 MHz to 869.85 MHz

Range

10 m (100 m in space)

Number of frequency channels 

7

Modulation technique

FSK (frequency shift keying)

Radiated power

5 dBm (3 mW)

German 

institute for 

construction 

technology

Содержание FA GC 150

Страница 1: ...mmis sioning operation and maintenance RSZ 6 RSZ 7 TS 4000 R TS 4000 RFS TS 4000 R IS TS 5000 R TS 5000 RFS TS 5000 RFS KB TS 5000 R ISM G S 0 TS 5000 R ISM EFS Slimdrive EMD F R Slimdrive EMD F R IS...

Страница 2: ...unted smoke detector ORS 142 23 4 9 Wireless ceiling mounted smoke detector GC 172 24 4 9 1 Signalling 25 4 9 2 Battery replacement 25 4 10 Wireless thermal detector GC 173 25 4 10 1 Signalling 26 4 1...

Страница 3: ...12 Hold open system Powerturn F R IS 53 5 8 13 Hold open system Powerturn F R IS TS 54 6 Commissioning 55 6 1 Check the self closing characteristic of the door 55 6 1 1 1 leaf door 55 6 1 2 2 leaf do...

Страница 4: ...terminal MRB Manual trigger switch manual release button NC Normally closed contact NO Normally open contact R Electric hold open device with lintel mounted de tector and power supply hold open syste...

Страница 5: ...gnificantly shorten the service life of the smoke switch The measuring chamber of a smoke switch must not be opened Fig 2 3 1 2 4 Disposal The hold open system is made up of materials that should be s...

Страница 6: ...nted detector Wireless input module Manual trigger switch Manual trigger switch Wireless input module Wirelessceiling mounted detector Manual trigger switch integrierte Festellanlage Rauchschaltzentra...

Страница 7: ...function E ISM guide rail 2 leaf with integrated closing sequence electromagnetic hold open function for both leaves E ISM G guide rail 2 leaf with integrated closing sequence electromagnetic hold ope...

Страница 8: ...ic hold open function or hold open function with hold open magnet TS 5000 R ISM guide rail 2 leaf with integrated closing sequence electromagnetic hold open function for both leaves TS 5000 R ISM G gu...

Страница 9: ...r Smoke detectors detect smoke They work using the scattered light principle A light transmitter and a light interface are arranged in the measuring chamber in such a way that no light reaches the int...

Страница 10: ...d directly above the door in the case of 2 leaf doors above the active leaf The lintel mounted smoke switch is installed in such a way that a minimum distance of 1 cm is observed between the upper edg...

Страница 11: ...ch mandatory The hold open devices TS 4000 EFS TS 5000 EFS ISM EFS guide rail Boxer EFS ISM EFS guide rail Boxer GT 50 R GT 60 R GT 63 R GT 70 R TSA 160 NT F TSA 160 NT F IS Slimdrive EMD F Slimdrive...

Страница 12: ...25 2008 06 DIN EN 1155 2006 06 DIN EN 62368 1 VDE 0868 1 2016 05 DIN EN 60950 1 2014 08 VDE 0805 1 2014 08 DIN EN 61000 6 2 2016 05 VDE 0839 6 2 2015 05 DIN EN 61000 6 3 2011 09 VDE 0839 6 3 2011 09...

Страница 13: ...le Alarm output Potential free relay output changer maximum 24 V DC maximum 1 A Test button The hold open device is switched off as long as the key is pressed for at least 4 s Reset of the smoke switc...

Страница 14: ...O 0 V 1 Display only if line monitoring is active jumper J3 2 Does not apply if the manual trigger switch is connected as a normally closed contact When the normally closed contact is actuated broken...

Страница 15: ...GC151 KL1 SW1 LED1 24V GND MRB AS 1 2 3 4 LED2 PB1 SW2 GC161 GC151 Fig 4 5 1 KL1 Connection to the lintel mounted smoke switch 24V Power supply GND Power supply MRB Manual trigger switch AS Ceiling m...

Страница 16: ...171 changes back to normal operation the displays are deleted and 24 V is applied to the hold open output of the lintel mounted smoke switch again Wireless module GC 171 operating mode Lintel mounted...

Страница 17: ...normal operation Low battery charge The wireless module GC 171 signals low battery charge if the voltage of the main battery of the corresponding wireless device falls to less than 2 6 V Both batteri...

Страница 18: ...V GND MRB AS 1 2 3 4 LED2 PB1 SW2 GC161 GC151 KL1 SW1 LED1 24V GND MRB AS 1 2 3 4 LED2 PB1 SW2 GC161 GC151 Set up wireless connection X X Slide a free wireless device switch SW1x of the wireless modul...

Страница 19: ...lide the set up switch on the new wireless device back and forward six times and start again with Install batteries X X Fit the wireless ceiling mounted detector to the base and close the housing of t...

Страница 20: ...151 X X Slide all 6 wireless device switches SW1x to the ON position The wireless device LED1x light up yellow in succession until all the wireless device switches are in the ON position They then fla...

Страница 21: ...unting Terminating resistors 2 43 k integrated can be disconnected Alarm output potential free relay output normally closed contact maximum 24 V DC maximum 1 A German institute for construction techno...

Страница 22: ...on Ceiling mounting Terminating resistors 2 43 k integrated can be disconnected Alarm output Potential free relay output normally closed contact maximum 24 V DC maximum 1 A Detector test Alarm trigger...

Страница 23: ...m 22 mA Installation position Ceiling mounting IP rating IP42 Ambient temperature 20 C to 60 C Alarm output Potential free relay output normally closed contact maximum 24 V DC maximum 1 A Magnetic hol...

Страница 24: ...or GEZE logo The LED flashes green Alarm triggering X X Move the test magnet near to the magnetic sensor GEZE logo again X X Trigger the alarm using the test aerosol The detector test using a test mag...

Страница 25: ...teries type CR123A make sure polarity is correct X X Replace the battery compartment cover 3 X X Insert the wireless detector into the base 8 X X Test the wireless detector It can take up to a minute...

Страница 26: ...on 5 s off Battery 2 discharged flashes green 0 1 s on 5 s off Both batteries discharged flashes orange green alternately 0 1 s on 5 s off Other faults flashes orange green alternately 0 5 s each Man...

Страница 27: ...Functional principle signals the state of an external potential free contact normally open contact to the GC 171 wireless module monitors the line to the contact for breaks Line length 130 mm Line mo...

Страница 28: ...5 s off each Contact closed short circuit flashes 1 x red 4 12 2 Battery replacement The wireless input module signals low battery charge to the wireless module GC 171 if the charge state of the batt...

Страница 29: ...h smaller than 15 m 6 J Y ST Y 2 2 0 6 mm or J Y ST Y 2 2 0 8 mm maximum length smaller than 6 m 7 J Y ST Y 2 0 6 mm or J Y ST Y 2 0 8 mm maximum length smaller than 3 m 8 J Y ST Y 2 2 0 6 mm or J Y S...

Страница 30: ...d smoke switch GC 151 5 2 1 Ceiling mounted detectors GC 152 and GC 153 The ceiling mounted smoke detector GC 152 is made up of the smoke detector GC 002 D and the relay base GC 150 B The ceiling moun...

Страница 31: ...nnect the breaking point in the base of the first ceiling mounted detector Ceiling mounted thermal detector GC 153 as lintel mounted detector with line monitoring If the lintel mounted smoke switch GC...

Страница 32: ...en two floor springs TS 550 E are used no more than two ceiling mounted detectors may be connected A A 5 5 5 Ceiling mounted detector Ceiling mounted detector Ceiling mounted detector as lintel mounte...

Страница 33: ...d smoke detector ORS 142 with line monitoring The general construction technique permit requires line monitoring to the ceiling mounted detectors Line monitoring is active if jumper J3 of the lintel m...

Страница 34: ...atory according to the standard see chap 3 5 3 Line monitoring is active if jumper J3 of the lintel mounted smoke switch to the measuring chamber is set 2 3 see chap 4 4 a 43 k resistor is connected i...

Страница 35: ...ch UTA The general construction technique permit requires line monitoring to the potential free contact of the fire alarm system and to the manual trigger switch Line monitoring is active if jumper J3...

Страница 36: ...itch SW2 of the wireless module GC 171 to the ON position see chap 4 5 See chap 4 5 2 for how to set up the wireless connections 5 4 1 Wireless ceiling mounted detector GC 172 or GC 173 and or wireles...

Страница 37: ...or wired wireless input modules GC 175 Ceiling mounted detectors are connected as described in chap 5 2 i n t e g r i e r t e F e s t e l l a n l a g e R a u c h s c h a l t z e n t r a l e R S Z 6 E...

Страница 38: ...e another e g installation of the two assemblies in two dif ferent flush mounted boxes 2 2 k GC 175 7 Fig 5 5 1 1 Several manual trigger switches are connected in parallel Only connect the 2 2 k resis...

Страница 39: ...the hold open system 24 V external Alarm display GND external Fig 5 6 1 5 7 Mutual triggering of two hold open systems Two hold open systems can trigger each other mutually For this purpose the alarm...

Страница 40: ...ernal hold open devices are connected to KL3 of the lintel mounted smoke switch system plug type con nection 5 8 1 Hold open system RSZ 6 RSZ 7 Door closer TS 4000 E TS 4000 EFS Door leaf installation...

Страница 41: ...Rem w 20 GC 151 Connector box TS 4000 E IS I 42 mA 24 VDC 15 Rem w 20 Door transmission Active leaf Passive leaf Door transmission 3 4 Switch closed if active leaf open Fig 5 8 1 3 Transom installatio...

Страница 42: ...f E hold open device active leaf 3 Fig 5 8 1 6 ISM EFS guide rail ISM EFS guide rail Boxer No hold open device for the passive leaf Connector box with plug in drip loop ID 052105 GC 151 Connector box...

Страница 43: ...lation 24 VDC 15 Rem w 20 I 42 mA 3 Fig 5 8 1 9 Integrated door closer Boxer EFS 24 VDC 15 Restw 20 I 80 mA Boxer EFS 3 Fig 5 8 1 10 Floor spring TS 550 NV E 24 VDC 15 Rem w 20 I 42 mA 3 Fig 5 8 1 11...

Страница 44: ...B ID 001102 Terminal box on site 24 VDC 1 0 Rem w 20 I 100 mA 24 VDC 1 0 Rem w 20 I 100 mA Active leaf Passive leaf 3 6 Connection board Switch closed if active leaf open Terminal box Fig 5 8 1 13 Hol...

Страница 45: ...F EN7 Accessories TSA 160 NT F ID 019654 Follow the wiring diagram for the TSA 160 NT swing door drive 3 Reset button Fig 5 8 1 15 Hydraulic swing door drive TSA 160 NT F IS Accessories TSA 160 NT F...

Страница 46: ...imdrive EMD F Follow wiring diagram for the Slimdrive EMD swing door drive 3 Fig 5 8 1 17 Electromechanical swing door drive Slimdrive EMD F IS Follow wiring diagram for the Slimdrive EMD swing door d...

Страница 47: ...ing door drive Powerturn F DCU8 DCU801 DCU802 DCU800 3 Fig 5 8 1 19 Electromechanical swing door drive Powerturn F IS Follow wiring diagram for the Powerturn swing door drive Powerturn F GF DCU8 DCU80...

Страница 48: ...rturn swing door drive Door closer Hold open magnet Reed switch 3 3 Reed switch closed if passive leaf is closed 3 Reset button Latching action cam Fig 5 8 1 21 5 8 2 Hold open system TS 4000 R TS 400...

Страница 49: ...TS 5000 R ISM G S 0 TS 5000 R ISM G no hold open function in the passive leaf TS 5000 R ISM S no hold open function in the active leaf TS 5000 R ISM 0 no hold open function in the passive and active...

Страница 50: ...passive leaf Connector box with plug in drip loop ID 052105 GC 151 Connector box Door trans mission TS 5000 EFS 3 Fig 5 8 6 1 5 8 7 Hold open system TS 5000 RFS Door leaf installation Connector box wi...

Страница 51: ...pen system FA GC 150 51 Wiring diagram 5 8 9 Hold open system Slimdrive EMD F R Follow wiring diagram for the Slimdrive EMD swing door drive Latching action cam 1 2 5 GND 24 V GND 24 V 5 Reset button...

Страница 52: ...or the Slimdrive EMD swing door drive 1 2 5 GND 24 V GND 24 V 3 5 3 Fig 5 8 10 1 5 8 11 Hold open system Powerturn F R Follow wiring diagram for the Powerturn swing door drive 1 2 5 GND 24 V Powerturn...

Страница 53: ...m 5 8 12 Hold open system Powerturn F R IS Follow wiring diagram for the Powerturn swing door drive 1 2 5 GND 24 V 3 Powerturn F GF DCU8 DCU801 DCU802 DCU800 Powerturn F SF DCU8 DCU801 DCU802 DCU800 3...

Страница 54: ...Follow wiring diagram for the Powerturn swing door drive 5 1 2 GND 24 V GND 24 V GND HOD DCU801 DCU8 Powerturn F GF DCU800 DCU802 55 56 2 51 PA 63 mA Reset button Latching action cam Hold open magnet...

Страница 55: ...af closes automatically The active leaf comes to a standstill and then closes when the passive leaf is closed 6 2 Testing the smoke detectors Test aerosol ID 059168 Systems may only be tested with an...

Страница 56: ...ZE ex pert training or specialists from an official test centre named by DIBt in the approval procedure The official acceptance test must include at least the following points 1 It must be checked tha...

Страница 57: ...see chapter 4 5 2 Connection quality Construction changes or new electronic assemblies in the direct vicinity of the hold open system can interfere with the wire less connections The charge state of t...

Страница 58: ...GEZE hold open system FA GC 150 58...

Страница 59: ...GEZE hold open system FA GC 150 59...

Страница 60: ...geze com www geze fr Hungary GEZE Hungary Kft E Mail office hungary geze com www geze hu Iberia GEZE Iberia S R L E Mail info es geze com www geze es India GEZE India Private Ltd E Mail office india...

Отзывы: