GEZE hold-open system FA GC 150
21
Technical data
4.6 Ceiling-mounted smoke detector GC 152
Smoke detector with relay base GC 152 ID 139850
comprising
ú
Relay base GC 150 B
ú
Smoke detector GC 002 D
Smoke detector GC 002 D
ID 141458
Colour
white, RAL 9016
Dimensions (with base, Ø × H)
110 mm × 67 mm
Functional principle
Scatter light, adaption of the alarm threshold, no alarm saving (self-reset-
ting as soon as there is no longer any smoke in the measuring chamber)
Insect grid
prevents insects getting into the measuring chamber.
Input voltage
24 V DC
Input current
maximum 20 mA
Installation position
Ceiling mounting
Terminating resistors
2 × 43 kΩ, integrated, can be disconnected
Alarm output
potential-free relay output, normally closed contact
maximum 24 V DC / maximum 1 A
German
institute for
construction
technology
Detector test
Alarm triggering
ú
with test magnet near the magnetic sensor (GEZE logo)
with test aerosol
The detector test using a test magnet tests the electrical compo-
nents. The detector test which forms part of the regular testing of
the hold-open system must be carried out using a test aerosol
(see chap. 6.2.2).
Signalling
LED
Relay output
Voltage-free
Off
24V
ASout
ASin
Normal
operation
Off
Alarm
Red
24V
ASout
ASin
Tab. 4.6.1
1
1
Fig. 4.6.1
3
2
GC 150 B
GND
AS
ou
t
ASin
24V
1
Fig. 4.6.2
1
Breaking point (see chap. 5.2)
2
Magnetic sensor for testing (behind the GEZE logo)
3
LED for displaying state