GEZE hold-open system FA GC 150
22
Technical data
4.7 Ceiling-mounted thermal detector GC 153
Thermal detector with base GC 153
ID 139881
comprising
ú
Relay base GC 150 B
ú
Thermal detector GC 003 D
Thermal detector GC 003 D
ID 141459
Colour
white, RAL 9016
Dimensions (with base, Ø × H)
110 mm × 67 mm
Functional principle
Alarm if the ambient temperature exceeds the alarm temperature or
if the ambient temperature increases very quickly, no alarm saving
(self-resetting as soon as the ambient temperature has dropped again)
Alarm temperature
57 °C
EN 54-5 classification
A1R
Input voltage
24 V DC
Input current
maximum 20 mA
Installation position
Ceiling mounting
Terminating resistors
2 × 43 kΩ, integrated, can be disconnected
Alarm output
Potential-free relay output, normally closed contact maximum 24 V DC /
maximum 1 A
Detector test
Alarm triggering
ú
with test magnet near the magnetic sensor
ú
with heat detector testing device
The detector test using a test magnet tests the electrical components.
The detector test which forms part of the regular testing of the hold-
open system must be carried out using a heat detector testing device
(see chap. 6.3).
Signalling
LED
Relay output
Voltage-free
Off
24V
ASout
ASin
Normal
operation
Off
Alarm
Red
24V
ASout
ASin
Tab. 4.7.1
1
1
Fig. 4.7.2
3
2
GC 150 B
GND
AS
ou
t
ASin
24V
1
Fig. 4.7.3
1
Breaking point (see chap. 5.2)
2
Magnetic sensor for testing (behind the GEZE logo)
3
LED for displaying state
German
institute for
construction
technology