7.2.2. CONNECTING THE DEVICE POWER SUPPLY
Protection devices
The circuit breaker and residual current protection devices required by the low voltage electrical system standard
must be installed upstream of the charging station.
If there are no indications concerning the residual current protection to be used, each station must be protected
by residual current circuit breakers installed upstream - either:
• Type B or
• Type A, fitted with a suitable device that ensures the disconnection of the power supply in the event of a DC
fault current higher than 6 mA
Wiring requisites
The connection must satisfy some requirements:
•
JOINON EASY HOME
Connection specifications
Type of connection
Single-phase
Number of wires
2P+E
Rated current
Up to 32A
Maximum wire diameter
10mm
2
•
JOINON EASY RFID / JOINON EASY CLOUD
Connection specifications
Type of connection
Single-phase/
three-phase
Number of wires
2P+E/3P+N+E
Rated current
Up to 32A
Maximum wire diameter
10mm
2