Setting the speed adjustment differential 1
Use the
or
button key to set the value of the adjustment
differential for the fan coil speed 1 (the gap can be set from 0°C
to 2,0°C). If a value of 0°C is set, then when the solenoid valve is
activated fan coil speed 1 will be instantaneously activated as well.
To confirm your choice and move on to the next parameter, press
the
button key within 30 seconds.
Setting the speed adjustment differential 2
Use the
or
button key to set the value of the adjustment
differential for the fan coil speed 2 (the gap can be set from 0,1°C
to 2,0°C). To confirm your choice and move on to the next
parameter, press the
button key within 30 seconds.
Setting the speed adjustment differential 3
Use the
or
button key to set the value of the adjustment
differential for the fan coil speed 3 (the gap can be set from 0,1°C
to 2,0°C). To confirm your choice and move on to the next
parameter, press the
button key within 30 seconds.
Setting the inertia for speed 1
Use the
or
button key to set the value of the inertia time for
the fan coil speed 1 (the gap can be set from 0 to 10 seconds). To
confirm your choice and move on to the next parameter, press the
button key within 30 seconds.
Setting the inertia for speed 2
Use the
or
button key to set the value of the inertia time for
the fan coil speed 2 (the gap can be set from 0 to 10 seconds). To
confirm your choice and move on to the next parameter, press the
button key within 30 seconds.
Setting the inertia for speed 3
Use the
or
button key to set the value of the inertia time for
the fan coil speed 3 (the gap can be set from 0 to 10 seconds). To
confirm your choice and move on to the next parameter, press the
button key within 30 seconds.
The setting of the timed thermostat parameters is now