5
Directives and Standards
DIN EN 14597
The temperature switch TRS 5-52 in conjunction with temperature sensor TRG 5-.. is type-approved to
DIN EN 14597.
DIN EN 14597 describes and specifies - among other things - the requirements made on tests of
temperature monitors.
ATEX (Atmosphère Explosible)
According to the European Directive 94/9/EC the equipment must
not
be used in explosion risk areas.
LV (Low Voltage) Directive and EMC (Electromagnetic Compatibility)
The equipment meets the requirements of the Low Voltage Directive 2014/35/EU and the EMC Direc-
tive 2014/30/EU.
UL / cUL (CSA) Approval
The equipment meets the requirements of the Directives: UL 508 and CSA C22.2 No. 14-13, Standards
for Industrial Control Equipment. File E243189.
Note
The temperature sensors TRG 5-63, TRG 5-64, TRG 5-65, TRG 5-66, TRG 5-67 and TRG
5-68 are simple items of electrical equipment as defined in EN 60079-11 section 5.7.
According to the European Directive 94/9/EC the equipment must be equipped with ap-
proved Zener barriers if used in potentially explosive areas. Applicable in Ex zones 1, 2
(1999/92/EC).
The equipment does not bear an Ex marking.
Note on the Declaration of Conformity / Declaration by the Manufacturer
For details on the conformity of our equipment according to the European Directives see our Declara-
tion of Conformity or our Declaration of Manufacturer.
The current Declaration of Conformity / Declaration of Manufacturer are available in the Internet under
www.gestra.com/documents or can be requested from us.