6
TRS 5-52
Supply voltage
24 VDC +/– 20 %
Fuse
external 0.5 A (semi-delay)
Power consumption
4 VA
Wiring temperature sensor
1 input for temperature sensor TRG 5-63, TRG 5-64, TRG 5-65, TRG 5-66, TRG 5-67 and TRG 5-68,
(platinum resistance thermometer Pt 100 to EN 60751), with 3 poles and screen.
Outputs:
2 volt-free change-over contacts, 8 A 250 V AC / 30 V DC cos
ϕ
= 1.
(MIN/MAX alarm, switchpoint adjustable).
Provide inductive loads with RC combinations according to manufacturer's specification to ensure
interference suppression.
1 analogue output 4-20 mA, max. load 500 ohm, e. g. for actual-value indication (optional).
Measuring range
0 °C up to 600 °C
Switching hysteresis
Switchpoint MAX temperature: –5 K, factory set.
Switchpoint MIN temperature: +5 K, factory set.
Indicators and adjustors
1 rotary button with integrated test button for MIN/MAX alarm and parameter settings,
1 four-digit seven-segment LED indication, green
2 red LEDs for MIN/MAX alarm
Housing
Housing material: base: polycarbonate, black; front: polycarbonate, grey
Conductor size: 1 x 4.0 mm
2
solid, per wire, or
1 x 2.5 mm
2
per stranded wire with sleeve to DIN 46228 or
2 x 1.5 mm
2
per stranded wire with sleeve to DIN 46228 (min.
∅
0.1 mm)
Terminal strips can be detached
Fixing of housing: Mounting clip on supporting rail TH 35, EN 60715
Electrical safety
Pollution degree 2 for installation in control cabinet with protection IP 54, completely insulated
Protection
Housing: IP 40 to EN 60529
Terminal strip: IP 20 to EN 60529
Weight
approx. 0.2 kg
Technical data