In the control cabinet: Electrically connecting the level controller
Wiring diagram of level controller NRR 2-51
5
Connection of supply voltage 24 V DC with 0.5A medium time-lag fuse provided by customer
6
Level transmitter NRGT 26-2, 4-20 mA, with grounding point.
Max. 3 NRS/NRR 2-5.. units can be connected (series connection).
7
Central grounding point (CGP) in control cabinet
8
MIN output contact, off delay 3 seconds
9
MAX output contact, off delay 3 seconds
0
Output 4-20 mA, manipulated variable Y
Key
6
NRR 2-51
Fig. 7
8
9
0
MAX
MIN
5
7
M0.5A
(medium
time-lag)