15
NRR 2-50, NRR 2-51 - USA - Installation & Operating Manual -
850699-00
Factory default settings
Level controller NRR 2-50
■
Off delay: 3 s
(default)
■
Input set as voltage input,
please change using code switch S3.
■
MAX switchpoint AL.Hi = 80%
■
MIN switchpoint AL.Lo = 20%
■
Set point SP = 50%
■
Proportional band Pb = 20% of
set point
■
Integral action time ti = 0%
■
Dead band = +/– 5% of set point
■
Valve travel time tt = 40 s
■
Calibration value CAL.P = 100%
■
Fill control function
■
MIN/MAX output contact set as MAX alarm
Code switch
c
: S1, S2, S3, S4 OFF
Level controller NRR 2-51
■
Off delay: 3 s
(default)
■
Input set as voltage input, please change
using code switch S3.
■
MAX switchpoint AL.Hi = 80%
■
MIN switchpoint AL.Lo = 20%
■
Set point SP = 50%
■
Proportional band Pb = 20% of
set point
■
Integral action time ti = 0%
■
Dead band = +/– 5% of set point
■
Calibration value CAL.P = 100%
■
Fill control function
Code switch
c
: S1, S2, S3, S4 OFF