6
NRA 1-3 / NRA 1-3 with CAN Bus interface
Technical Data
Supply voltage
230 V, 50 / 60 Hz
115 V, 50 / 60 Hz optional
Only
NRA 1-3 with CAN Bus interface
Supply voltage
24 V DC +/- 20 % via CAN Bus interface
Data exchange
CAN bus to ISO 11898, CANopen protocol
NRA 1-3 and NRA 1-3 with CAN bus interface
Fuse
external, slow-blow 200 mA
Power consumption
max. 5 VA
Inputs
16 inputs for measuring electrodes NRG 16-19, NRG 16-27, NRG 16-28
1 input for temperature sensor, e. g. TRG 5-53, measuring insert PT 100
max. length of connecting cables: 100 m
Output
1 volt free changeover contact, 4 A 24 V AC/DC, 115 V AC and 230 V AC
Inductive loads must be provided with interference suppressors (RC combinations) as specified by the
manufacture
Electrode voltage
12 V
Settings for banking-up of condensate
Difference between condensate and plant temperatures
dts
1 K to 100 K, adjustable in steps of 1 K
(mode 1 and 6)
Difference between condensate temperature and switchpoint "Banking-up of condensate"
dtC
1 K to 100 K, adjustable in steps of 1 K (mode 2 and 7)
Switchpoint "Banking-up of condensate" 0 °C to 255 °C,adjustable in steps of 5 K (mode 2 and 7)
Indicators and adjustors
1 three-digit seven-segment LED display, red, for indicating faulty steam traps and status and error
messages
3 LEDs for indicating banking-up of condensate, steam loss and malfunction in measuring electrode
3 pushbuttons for operating the equipment
1 ten-pole code switch for system configuration, node ID and baud rate setting
Versions
NRA 1-3a for wall mounting
NRA 1-3e for panel mounting
Housing material: ABS
Protection
NRA 1-3a: IP 65 to EN 60529
NRA 1-3e: Front: IP 65 to EN 60529, back: IP 00
Protection
NRA 1-3a: 2 (completely insulated)
Admissible ambient temperature
Max. 55 °C