18
The precondition for this operating mode is:
the use of the measuring electrodes NRG 16-27, NRG 16-28 (with integrated condensate tempera-
ture measurement at the steam trap) and
the use of a separate temperature sensor for the measurement of the system/(plant) temperature.
With the parameter
dtS
you can change the difference between the condensate temperature in the
steam trap and the plant temperature for all steam traps
ALL
or for each individual trap (C.xx). The
factory set default value is 40 K. The value can be changed in increments of 1 K and must between
between 0 and 100 K.
With the parameter
tlo
you can set the lower temperature limit between 0 and 100 °C in increments of
5 K. If the condensate temperature is below the temperature limit, the alarms "Banking-up of conden-
sate" and "Steam loss" will neither be indicated nor stored.
Operation, alarm and test
Setting banking-up of condensate, mode 1 to 6
SYS / °C
Press key E
briefly
→
←
longer
HIS
Keys
(1)
↓
(3)
↑
InT
Keys
(1)
↓
(3)
↑
dtS
Press key E
briefly
→
←
longer
ALL
Press key E
briefly
→
←
longer
Change
tem-
perature
keys (1),(3)
Press key
E briefly
→
don
←
dtS
Keys
(1)
↓
(3)
↑
Keys
(1)
↓
(3)
↑
C.xx
Press key E
briefly
→
←
longer
Change
tem-
perature
keys (1),(3)
Press key
E briefly
→
don
←
C.xx
tlo
Press key E briefly
→
←
longer
Change
temperature
keys (1),(3)
Press key
E briefly
→
don
←
tlo
- continued -