17
Operation, alarm and test
Mode 1, 6:
After the mains voltage has been switched on and the display test has been finished the
system temperature, error messages and current alarms will be indicated.
Mode 2 to 5 and 7:
After the mains voltage has been switched on and the display test has been
finished error messages and current alarms will be indicated.
For more information on the codes HIS, Int and tSt see section “Alarm list, Maintenance interval and
Test”, mode 1 to 7 (page 23).
Start
For the communication with the CAN bus each bus node requires an own address (node ID) and baud
rate (speed of data transfer) setting.
The cable length between the bus nodes dictates the baud rate setting.
Cable length
Baudrate
125 m
250 kBit/s (factory setting)
250 m
125 kBit/s
335 m
100 kBit/s
500 m
50 kBit/s
1000 m
20 kBit/s
Please make the following settings:
Briefly press the E key and then key 1 until CAN is indicated on the seven-segment display. Enter the
baud rate and node ID settings.
For the node ID you can use numbers between 1 and 127.
If the baud rate and/or the node ID settings are changed the new values will only become active after
switching the power supply voltage to the test station off and on again.
Only for NRA 1-3 CAN: Setting node ID and baud rate
Start
Press key E
briefly
→
←
longer
HIS
Keys
(1)
↓
(3)
↑
CAN
Press key E
briefly
→
←
longer
BR
Press key E
briefly
→
←
longer
Change
indi-
cation
keys (1),(3)
Press key
E briefly
→
don
←
CAN
Keys
(1)
↓
(3)
↑
ID
Press key E
briefly
→
←
longer
Change
tem-
perature
keys (1),(3)
Press key
E briefly
→
don
←
ID
- continued -
Содержание NRA 1-3
Страница 29: ...29 For your Notes ...
Страница 30: ...30 For your Notes ...
Страница 31: ...31 For your Notes ...