36
System malfunctions
- continued -
Error message 4
LED Power is flashing slowly
Fault:
The power supply unit in the control device is overloaded!
Remedy:
Test the supply voltage for all CAN bus systems. The two end-of-line devices must be
supplied with a voltage of > 24 V DC. If this is not the case check the supply voltage of
the CAN bus; see section “Electrical Connection”.
Cut off power supply and restart system.
Fault:
Power supply unit in control unit defective!
Remedy:
Replace control unit.
Decommissioning
Danger
The terminal strips of the equipment are live during operation.
This presents the risk of severe cases of electric shock!
Cut off power supply to the equipment before mounting or removing the terminal strips!
1. First detach terminal strips
0
. For this purpose turn the right and left fixing screw
!
in direction of
the arrow until the terminal strip can be detached.
2. Undo the fixing slide, snap out the controller and take it off the supporting rail
§
.
3. When ordering spare parts please state the serial number indicated on the name plate.
4. Write down the parameters set in the operating panel URB / SPECTOR
control
and enter them in the
new control unit LRR 1-40 after installation.
Replacing control unit
Disposal
Dismantle the equipment and separate the waste materials, using the material specification as a
reference.
Electronic component parts such as the circuit board must be disposed of separately!
For the disposal of the equipment observe the pertinent legal regulations concerning waste disposal.