9
Technical Data
- continued -
LRR 1-40
- continued -
24 h purging pulse
Forced opening of the continuous blowdown valve every 24 hours, adjustable.
Automatic intermittent blowdown
Intermittent blowdown interval (duration of break): 1 - 120 hours, adjustable in steps of one hour.
Duration of intermittent boiler blowdown: 1 - 60 seconds, adjustable in steps of one second.
Pulses of intermittent boiler blowdown: 1 - 5, adjustable in steps of one.
Pulse interval: 5 - 30 seconds, adjustable in steps of one second.
Mains voltage
230 V +10 / –15 %, 50 – 60 Hz
115 V +10 / –15 %, 50 – 60 Hz (optional)
24 V +10 / –15 %, 50 – 60 Hz (optional)
Power consumption
10 VA
Protection
Housing: IP40 to EN 60529
Terminal strip: IP20 to EN 60529.
Max. admissible ambient temperature
0 – 55 °C
Body material
Front panel: polycarbonate, grey
Body: polycarbonate, black
Weight
approx. 0.8 kg