Factory setting
The control unit LRR 1-40 features the following factory set default values:
Control parameters
Setpoint W: 5000 μS/cm
Switching hysteresis of controller output (configuration as 2-position controller): 10 %
Operating position of continuous blowdown valve: 8 %
Proportional range X
p
: 0 %
MAX switchpoint (Hi): 7000 μS/cm
MIN switchpoint (Lo): 1000 μS/cm
Automatic intermittent blowdown: Off
24-h purging pulse: Off
System settings
Baud rate:
250 kBit/s for 125 m bus line
Node ID: 50
Enter the assigned node ID on the name plate.
Basic Settings
- continued -
Establishing / changing node ID
If several identical systems are to communicate in a CAN bus network, allocate a different node ID for
each system (e. g. limier, controller, etc). In most cases it is sufficient to commission the equipment
with the default factory settings.
To set the code switch
9
remove the lower terminal strip
0
.
Attention
We recommend that you commission the CAN bus devices with the default factory
setting.
Do
not
use a node ID for more than one piece of equipment in the CAN bus system!