34
System malfunctions
- continued -
Error message 1
Fault:
The initialising phase has not been finished during start-up.
No communication with conductivity electrode!
Remedy:
Check wiring, node ID, baud rate setting and bus cable.
Cut off power supply and re-start system after 5 sec.
LEDs 1 to 3 (4 for MIN limit) are flashing
rapidly
A communication error has been detected.
LEDs 1 to 3 (4 for MIN limit) are flashing slowly.
Fault:
Measuring surface(s) of conductivity electrode is exposed.
Remedy:
Check installation and make sure that the measuring surface is submerged
Fault:
Internal wires of the conductivity electrode are defective or the temperature sensor failed.
Remedy:
Replace conductivity electrode.
Fault:
The temperature in the terminal box of the conductivity electrode exceeds the specified
limit.
Remedy:
Check installation of electrode and, if necessary, protect the equipment against exces-
sively high temperatures. As soon as the temperature falls below the max. admissible
limit, the equipment switches back to operating mode.
Error message 2
1
2
3
4
Test
P
1
2
3
E
4
µS
ppm
GESTRA
LRR 1-40