Troubleshooting
Problem
Cause
Remedy
Loud noise
The equipment is operating in the
unstable range of the volume flow
with the swing disk oscillating.
Raise the volume flow by increasing the
pump capacity.
Install the equipment at a different
position.
The distance between the
equipment and the pump is too
short.
Increase the distance of the equipment
so that a stabilized flow is provided.
The swing disk touches the pipe. Align the equipment.
Install the equipment at a position where
the swing disk does not touch the pipe.
Install an equipment that is suitable for
the pipe.
Equipment leaks
The equipment is damaged.
Check the condition of the equipment.
Replace the equipment if it is damaged.
The spring is damaged or worn. Check the condition of the springs.
Replace any damaged or worn spring.
A gasket is damaged.
Check the condition of the gaskets.
Replace any defective gasket.