Instruction manual - ProcessX
,QFDVHRIDEVROXWHDQGJDXJHSUHVVXUHWUDQVPLWWHU).$DQG).*
$EVROXWHSUHVVXUHWUDQVPLWWHU).$
*DXJHSUHVVXUHWUDQVPLWWHU).*
%ROWVL]H
%ROWPDWHULDO
7LJKWHQLQJWRUTXH
0D[LPXPZRUNLQJSUHVVXUH
M10
Cr-Mo steel
50 N.m
500 bar
M10
SS 316
30 N.m
100 bar
M12
Cr-Mo steel
60 N.m
500 bar
M12
SS 660
60 N.m
500 bar
M16
SS 660
110 N.m
500 bar
%ROWVL]H
%ROWPDWHULDO
7LJKWHQLQJWRUTXH
0D[LPXPZRUNLQJSUHVVXUH
M10
Cr-Mo steel
50 N.m
30 bar
M10
SS 316
30 N.m
30 bar
M10
SS 630
50 N.m
30 bar
Nut
Seal diaphragm
Gasket
Oval flange sureface
Measurement
chamber cover
Bolt
To avoid any damage of the measuring cell, do not exceed the test pressure
of the different cells (please refer to the technical datasheets of the concerned
transmitter)
(1) Remove the 4 hexagon sockets head bolts
(2) The process covers, the O-ring and the bolts and nuts can now be removed
(3) After disassembly, replace the faulty part with a new one
(4) Before reassembly, clean carefully the O-ring face of casing cover with the soft cloth im-
mersed in water, alcohol, or similar
(5) Reassemble the detecting unit by reversing the disassembling procedure. The torque of the
bols of the process covers are indicated in the following table
(6) After assembly, carry out a pressure test. Apply a pressure equal to 150% of the maximum
ZRUNLQJSUHVVXUHWRERWKÀDQJHVLGHKLJKSUHVV3DQGORZSUHVVXUH/3PHD
-
surement chamber of the transmitter simultaneously during 15 minutes, and make sure
there is no leakage.