Instruction manual - ProcessX
Recommendation for process connection
*DVPHDVXUHPHQW
Locate the process tap above the pressure source
OLTXLGPHDVXUHPHQW
Locate the process connection below the pressure
tap and the remote seal must be located below
this one.
/HYHOPHDVXUHPHQWRQRSHQWDQN
+
1
must be more than half of the remote seal
diaphragm diameter. Otherwise the measure will
not be linear to the level as far as the diaphragm
is not totally submerged.
Isolatingvalve
Remote seal
Atmospheric
air leak valve
Process connection
Pressure tap
Transmitter
H
1
h
D
ρ
ρ
Max. liquid
level
Min. liquid
level
Isolating
valve
Remote seal
Transmitter
Pressure tap
Isolating valve
Transmitter
Process connection
Atmospheric air
leak valve
remote seal
It is recommanded to install the transmitter below the remote seal(s). it
becomes necessary if process pressure is less than atmospheric pressure.
In order to prevent vibration of the transmitter body and capillary from in-
terfering with output, the transmitter body should be installed at a vibration
IUHHSODFHDQGWKHFDSLOODU\VKRXOGEH¿[HGWRDVWDEOHVXSSRUW