fu-processx-en 103
www.georgin.com
Instruction manual - ProcessX
7.4 Adjustment after replacement of the amplifier unit or the measuring cell
$GMXVWPHQW
After completion of the assembly work mentioned above, use the following procedures for
DGMXVWPHQWDQGVHWWLQJ$GMXVWPHQWVKRXOGEHSHUIRUPHGX+&
(1) After replacement of electronics unit (including replacement of internal parts)
No.
,WHP
'LVSOD\V\PERO
RIORFDOFRQ¿JX
UDWRUXQLWZLWK
/&'GLVSOD\
5HOHYDQW
SDJH
'LVSOD\V\PERORI
+&&
5HOHYDQW
SDJH
&RQWHQWVRIVHWWLQJDGMXVWPHQW
1
TAG No.
1 : TAG
(P47)
1 : TAG No.
(P75)
Set the previous data before replacement of
amp unit.
2
Model code
2 : TYPE
(P48)
2 : TYPE
(P75)
Set the previous data before replacement of
amp unit.
3
Serial No.
3-1 : SERIAL No.
3-2 : VER
(P49)
3 : SERIAL No.
(P76)
Not necessary for operation
4
Engineering unit
4: UNIT
(P50)
4: UNIT
(P76)
Set the previous data before replacement of
amp unit.
5
Range limit
5: URL
(P50)
5 : RANGE LIMIT
(P77)
Not necessary for operation
6
Measuring range
6-1 : LRV
6-2 : URV
(P51)
6 : RANGE
(P77)
Set the previous data before replacement of
amp unit.
7
Damping
7 : DAMP
(P53)
7 : DAMPING
(P78)
Set the previous data before replacement of
amp unit.
8
Output mode
8-1 : OUT Md
8-2 : CUT Pt
8-3 : CUT Md
(P54)
8 : OUTPUT MODE
(P79)
Set the previous data before replacement of
amp unit.
9
Burnout direction
9-1 : BURNOUT
9-2 : OVER
9-3 : UNDER
(P56)
9 : BURNOUT
(P80)
Set the previous data before replacement of
amp unit.
10
Zero/span
calibration
A-1 : ZERO
A-2 : SPAN
(P58)
A: CALIBRATE
(P81)
Implement span calibration after zero calibra-
tion.
11
Calibration output
circuit
b-1 : 4 mAAdj
b-2 : 20 mAAdj
b-3 : FIXcur
(P60)
B : OUTPUT ADJ
(P82)
Loop check & calibrate fixed output current
(4mA,20mA)
12
M e a s u r e m e n t
data
(Normal mode)
(P61)
C :DATA
(P83)
Check the measurement data.
13
Self-diagnosis
d1 : AMPTMP
G$/0&+.
(P62)
'6(/)&+(&.
(P83)
Check, if it is necessary.
14
Printer function
-
E: PRINT
(P84)
,+&ZLWKSULQWHURSWLRQSULQWLILWLV
necessary.
15
L o c k o f a d j u s t -
ment functions
F : LOCK
(P62)
F : XMTR EXT.SW
(P84)
Set the previous data before replacement of
amp unit
16
Indication of
digital indicator
G-1 : LDV
G-2 : UDV
G-3 : DP
G-4 : LcdUnit
G-5 : LcdOpt
(P63)
G : XMTR DISPLAY
(P85)
Set the previous data before replacement of
amp unit.
17
Programmable
linearization
function
-
+/,1($5,=(
(P87)
Set the previous data before replacement of
amp unit.
18
I n p u t - o u t p u t
range adjustment
I-1 : LRVAdj
I-2 : URVAdj
(P66)
I : RERANGE
(P89)
Adjust the input-output range (RERANGE) as
required.
19
Change of
saturation current
J-1 : SAT LO
-6$7+,
J-3 : SPEC
(P68)
J : SATURE CUR
(P90)
Set the previous data before replacement of
amp unit.
20
Protective func-
tion of set value
K: GUARD
(P70)
K : WRITE PROTCT
(P91)
Set the previous data before replacement of
amp unit.
21
+LVWRU\ LQIRUPD
-
tion
/+LV=(52
/+LV63$1
/+LV&/($5
/+LV$03
/+LV&(//
(P71)
K : WRITE PROTCT
(P92)
Check data as necessary
(2) After replacement of detecting unit (including replacement of internal parts)
1
Zero/span
calibration
A-1 : ZERO
A-2 : SPAN
(P68)
A : CALIBRATE
(P81)
Implement span calibration after zero
calibration.