8.
REDUNDANCY
Redundancy can be roughly divided in two types: serial (hot standby) redundancy
and parallel (active) redundancy. The T3UPS series adopts mainly serial redundancy.
8.1. Serial Redundancy
ONE TO ONE SERIAL REDUNDANCY
Serial (hot standby) redundancy consists of two UPS with one UPS’s (UPS1)
connected to the reserve/bypass input of the other UPS (UPS2). See the above
figure.
8-1