When installing GENVEX Premium-series
and Premium range, please follow these
instructions:
1) Make sure that the machine is in plumb.
2) Install an airtight water trap on a non-freezing
location to compensate for fan pressure.
3) The height of the water trap must be at least
100 mm.
4) Make sure that the drain flows downwards all
the way from the unit.
5) Pour some water into the drip tray of the unit
to verify that it functions properly.
6) If freezing of the water trap may occur, it
is necessary to install a thermostat and an
electrical heater to prevent freezing when the
.
IMPORTANT
.
IMPORTANT
.
IMPORTANT
.
IMPORTANT
.
IMPORTANT
.
.
IMPORTANT
.
IMPORTANT
.
IMPORTANT
.
IMPORTANT
.
IMPORTANT
.
temperature drops below +2C°.
7) Air flow adjustments must be made on both
the supply and exhaust side prior to normal
use of the machine. It is important to have
a balance between supply and exhaust air
volumes
8) It is recommended to keep the ducts closed
until the unit is adjusted and working.
This instruction must be followed. If the drain is
not made according to this instruction GENVEX
A/S cannot be made responsible for any additio-
nal damages, which have nothing to do with the
GENVEX unit.
Fresh air
Exhaust air
Extract air
Supply air
Airtight connection
100 mm
Air tight connection
Inside outlet
Illustration applie to the Premium range
3