6

  

Installation

Duct insulation, alt. A

Duct insulation, alt. B

Faulty duct insulation

Condensate drain

The units produces up to 5-8 litres of condensate per 

day. It is therefore important that the condensate drain is 

correctly made and that the unit has a slight fall towards 

the condensate drain. The condensate drain pipe must 

be mounted with the necessary gradient and be led to an 

internal outlet. The condensate drain must be fitted with a 

water trap as there is negative pressure in the air chamber 

in which the condensate tray is mounted.

If the unit is installed in a cold loft space, the condensate 

drain pipe must be insulated to prevent freezing of the 

condensate in the pipe.

However, it is recommended that the water trap is installed 

in a heated space to ensure that the water does not freeze.

If installation problems make it impossible to secure the 

condensate drain pipe from freezing by insulation, it will be 

necessary to mount a thermostat-controlled heating coil 

round the condensate drain pipe.

Insulation of ducts in cold loft spaces

In order to high recovery rate of the unit, it is necessary to 

insulate the ducts correctly. Supply and extract ducts:

Supply and extract air duct :

To minimize heat losses from the duct system in cold loft 

spaces, the supply and extract ducts must be insulated with 

minimum a 100 mm insulation mat. If insulation type A is 

chosen, it is recommended that it is done with two layers of 

50 mm mats wropped with paper or foil on the outside and 

with staggered joints between the two layers. If the ducts 

are positioned on the rafter foot, type B may be chosen. 

The insulation must always be tightly wrapped round the 

ducts.

Fresh air and exhaust air ducts in cold spaces : 

It is recommended that fresh air and exhaust air ducts 

are insulated with a minimum of 50 mm insulation. The 

fresh air duct is insulated to prevent warm air in the loft in 

summer from heat up the fresh air. Make sure to seal the 

termination where the escaping duct is led through the roof 

or through the gable end in order to avoid condensation 

damage.

Fresh air

Exhaust air

Extract air

Supply air

Airtight connection

100 mm

Air tight connection

Inside outlet

No water in siphon:

= Outlet is blocked

= Underpressure which leeds to 

false air

Содержание GE Premium 1/1L

Страница 1: ...Version V1 04 0310 GB Installations Manual Active Ventilation Heat pump GES Premium 1 1L GE Premium 1 1L GE Premium 2 GE Premium 3...

Страница 2: ...ts in cold loft spaces 6 Insulation of ducts in heated spaces 7 Electrical installation 7 Commissioning of the unit 8 Maintenance of the unit 8 Fault finding 10 Electrical diagram GE Premium serie 11...

Страница 3: ...ing when the IMPORTANT IMPORTANT IMPORTANT IMPORTANT IMPORTANT IMPORTANT IMPORTANT IMPORTANT IMPORTANT IMPORTANT temperature drops below 2C 7 Air flow adjustments must be made on both the supply and e...

Страница 4: ...ons from the unit cannot be transferred through ceiling and walls and so that the condensate drain with the necessary water trap can be led to an inside drain without danger of freezing in cold weathe...

Страница 5: ...commended that the duct system is made of spiral ducting with rubber ring seal fittings in order to provide a tight and durable duct system To achieve a satisfactory low sound level from the unit sile...

Страница 6: ...ducts in cold loft spaces In order to high recovery rate of the unit it is necessary to insulate the ducts correctly Supply and extract ducts Supply and extract air duct To minimize heat losses from...

Страница 7: ...easuring equipment If you wish to start up the unit before adjustment do as follows Before starting up the unit 1 Make sure that the Genvex unit is correctly mounted and that all ducts are insulated a...

Страница 8: ...el flashes the filters must be changed cleaned Stop the unit on the switch on the unit or the electrical panel Open the front cover and take out the filter When the filter has been changed or cleaned...

Страница 9: ...heck the two fan wheels for dirt If they are dirty they may be cleaned with a brush bottle washer etc Supply and extract valves Clean the valves by wiping them with a dry cloth Make sure the valve doe...

Страница 10: ...living rooms Fault Defect fan Blocked filter Fresh air grill is blocked by dirt and leaves in the autumn or snow and ice in the winter Fuse on control circuit board has blown No extract air from wet r...

Страница 11: ...Costumer Yours ref Construct KS Order no Our ref Rev Type GES Premium 1 and 2 EC Date 23 02 20 Page 1 of 1 Serial...

Страница 12: ...Premium range Evaporator cooling coil High pressure switch Condenser heating coil MA4 Compressor Control panel MA7 HP Exhaust Air Supply Air T4 T5 T3 T6 T1 T7 T2 Extract Air Fresh Air Counter current...

Страница 13: ...13 Notes...

Страница 14: ...14 Notes...

Страница 15: ...15 Notes...

Страница 16: ...m Artiklima bvba B 9220 Hamme Tel 32 0 52 41 25 41 Fax 32 0 52 41 29 66 E Mail info artiklima be Great Britain Total Home Environment Ltd GB Moreton in Marsh GL 56 0JQ Tel 44 0 845 260 0123 Fax 44 0 1...

Отзывы: