4
Installation
Dimensions in mm
Installation
The GE Premium range is available with supply air on the
right-hand side (as shown) or supply air on the left-hand
side and as a reversible cool/heat exchanger.
When it is a left-hand version the unit is build laterally
reversed, which means that the power connection is placed
on the left-hand side.
Because it is a reversible heat pump the unit has two
condensate drains. At all times the condensation from the
heat pump will appear. Both outlets must be connected to a
suitable drain on site.
The unit must be positioned on a surface so that vibrations
from the unit cannot be transferred through ceiling and
walls and so that the condensate drain with the necessary
water trap can be led to an inside drain without danger
of freezing in cold weather. In the winter period the unit
may produce up to 5-8 litres of condensate each day. To
allow access for service and maintenance, there must be
a space of a minimum of 600 mm in front of the unit and
a current floor. If the unit is located in the loft space, there
must be free access to the unit from the loft hatch.